{"name":"煤矿井下电气作业题库","level":"待补充","org":"应急管理部门","count":300,"questions":[{"id":1,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面有轻微锈蚀时，正确的处理方式是","options":["用砂纸打磨平整后涂防锈油","用棉纱擦净后涂薄层凡士林","用刮刀刮除锈迹后直接装配","用钢丝刷除锈后涂油漆封闭"],"answer":[1],"explanation":"知识点：隔爆结合面维护要求。隔爆结合面轻微锈蚀应用棉纱擦净并涂薄层凡士林防锈，不能损伤结合面精度。A砂纸打磨会改变结合面间隙；C刮刀刮除同样破坏结合面；D钢丝刷除锈加涂油漆会增大间隙并影响隔爆性能。"},{"id":2,"type":"single","stem":"井下低压馈电开关中，检漏保护装置动作后恢复送电前必须先做的工作是","options":["将开关手柄打到合闸位置试送一次","查明并排除漏电故障点","把检漏继电器退出运行后送电","测量电网绝缘电阻并记录数值"],"answer":[1],"explanation":"知识点：漏电闭锁与故障处理程序。检漏保护动作说明电网存在漏电故障，必须先查明并排除故障点才能恢复送电。A未排除故障试送电可能引发事故；C退出检漏属于甩保护运行；D测绝缘是排查手段之一，但单纯测量记录不能代替排除故障。"},{"id":3,"type":"single","stem":"矿用隔爆型电气设备接线嘴与电缆之间密封圈的正确使用方法是","options":["密封圈内径与电缆外径配合、厚度符合要求","密封圈内径略大于电缆外径便于穿入","密封圈割开两半套在电缆上再压紧","密封圈内径略小于电缆外径以增加密封"],"answer":[0],"explanation":"知识点：隔爆接线嘴密封圈配合要求。密封圈内径应与电缆外径配合、厚度符合规定，才能保证隔爆性能。B内径过大会留间隙失去隔爆作用；C割开套入破坏密封圈完整性；D内径过小会挤压电缆绝缘并难以装配到位。"},{"id":4,"type":"single","stem":"井下电气设备运行中隔爆外壳温度异常升高，最可能的原因是","options":["外壳接地电阻偏大","内部接线接触不良发热","周围空气湿度偏高","设备安装位置偏高"],"answer":[1],"explanation":"知识点：电气设备过热故障判断。外壳温度异常升高多因内部接线接触不良、触点电阻增大发热所致。A接地电阻偏大影响保护动作而非直接引起外壳发热；C湿度高影响绝缘但不直接导致外壳温度异常升高；D安装位置高低与发热无直接因果关系。"},{"id":5,"type":"single","stem":"井下电缆连接时，两根电缆芯线采用压接连接后，对接头绝缘处理的要求是","options":["缠绕绝缘胶带后即可投入运行","压接后涂导电膏直接裸露","接头绝缘强度不低于电缆本体绝缘","接头处用热缩管收缩后不密封"],"answer":[2],"explanation":"知识点：电缆接头绝缘恢复要求。接头绝缘强度应不低于电缆本体绝缘，才能保证安全运行。A仅缠绕胶带通常达不到本体绝缘水平；B裸露接头会短路或漏电；D热缩管收缩后仍需密封防潮，不密封不能保证绝缘性能。"},{"id":6,"type":"single","stem":"井下电气作业中，验电环节使用与电源电压等级相符的验电器验明无电后，下一步应做的是","options":["立即用手触碰导体确认","对可能来电侧装设接地线","直接开始拆卸设备螺栓","测量导体对地电阻值"],"answer":[1],"explanation":"知识点：停电作业安全程序。验明无电后应立即对可能来电的各侧装设接地线，防止突然来电。A用手触碰极其危险；C未装接地线就拆设备违反程序；D测电阻不能替代装设接地线。"},{"id":7,"type":"single","stem":"矿用隔爆型电磁起动器在运行中出现频繁跳闸，检查发现过流整定值偏小，正确的处理是","options":["将整定值调到最大后继续运行","按负荷实际电流重新整定并试验","短接过流保护接点临时运行","更换更大容量熔断器后送电"],"answer":[1],"explanation":"知识点：过流保护整定与故障处理。应按负荷实际电流重新整定并做动作试验。A调到最大可能失去保护作用；C短接保护接点属于甩保护；D更换大熔断器不能解决整定值偏小问题且可能失去保护。"},{"id":8,"type":"single","stem":"井下照明综保装置漏电试验按钮按下后装置不动作，正确的判断处理是","options":["试验按钮损坏，更换按钮即可","装置可能失去漏电保护功能，应停电检修","电网绝缘良好所以不动作","漏电试验周期未到所以不动作"],"answer":[1],"explanation":"知识点：漏电保护装置试验与故障判断。试验按钮按下不动作说明保护功能可能失效，应停电检修。A仅换按钮未必解决保护失效；C绝缘良好时试验应正常动作；D试验按钮动作与周期无关。"},{"id":9,"type":"single","stem":"井下电气设备检修时，验电、放电后对可能积聚瓦斯的地点进行瓦斯检查，瓦斯浓度低于规定值方可","options":["直接送电试运行","进行导体裸露作业","拆除接地线","恢复设备外壳"],"answer":[1],"explanation":"知识点：井下电气检修与瓦斯管理。瓦斯浓度低于规定值方可进行导体裸露作业，防止产生火花引燃瓦斯。A送电试运行还需完成其他程序；C拆接地线应在作业结束后按程序进行；D恢复外壳与瓦斯检查无直接先后关系。"},{"id":10,"type":"single","stem":"某矿掘进工作面局部通风机电源开关突然跳闸，电工到现场后发现开关内部有焦糊味，正确的处置是","options":["复位后立即试送电观察","断开上级电源后开盖检查","用绝缘电阻表测量后直接送电","更换开关外壳后送电"],"answer":[1],"explanation":"知识点：电气故障现场处置程序。开关内部有焦糊味说明可能存在绝缘损坏或短路，应先断开上级电源再开盖检查。A复位试送可能扩大故障；C未查明原因直接送电危险；D仅换外壳不能排除内部故障。"},{"id":11,"type":"single","stem":"井下移动变电站低压侧馈出电缆被掘进机压伤，外护套破损但芯线未见裸露，跟班电工的正确处置是","options":["用绝缘胶带缠绕破损处后继续供电","立即停止该回路供电并更换电缆","降低该回路负荷后继续运行","将破损段盘起悬空后继续供电"],"answer":[1],"explanation":"知识点：电缆损伤处置。外护套破损可能伤及绝缘，应立即停止该回路供电并更换电缆。A缠绕胶带不能保证绝缘和机械强度；C降负荷不能消除绝缘隐患；D盘起悬空不能修复已受损的绝缘。"},{"id":12,"type":"single","stem":"井下电气设备运行中出现外壳温度明显升高但未冒烟，电钳工应首先采取的措施是","options":["立即切断电源并挂牌检查","继续观察半小时再决定","打开外壳通风散热","记录温度后汇报等待指令"],"answer":[0],"explanation":"知识点：电气设备异常温升处置。温度异常升高可能由过载、接触不良或短路引起，应立即断电检查。B项继续观察可能扩大故障；C项带电开盖违反操作规程且可能引发爆炸；D项未断电存在事故隐患。"},{"id":13,"type":"single","stem":"某矿掘进工作面照明综保装置漏电试验不动作，经查是试验按钮接触不良，正确的处置是","options":["更换试验按钮后重新做漏电试验","短接试验回路让保护动作","调整漏电整定值使其灵敏","停用漏电试验功能继续供电"],"answer":[0],"explanation":"知识点：漏电保护装置故障处置。试验按钮接触不良应更换后重新试验确认保护功能正常。B项短接试验回路会掩盖真实保护性能；C项调整整定值不能解决按钮故障且可能误动；D项停用漏电试验严重违反安全规定。"},{"id":14,"type":"single","stem":"井下防爆电气设备接线嘴与电缆之间必须使用密封圈，密封圈内径与电缆外径的配合要求是","options":["密封圈内径与电缆外径应一致","密封圈内径可比电缆外径大2mm","密封圈内径可比电缆外径小1mm","密封圈内径与电缆外径允差不超过5mm"],"answer":[0],"explanation":"知识点：防爆密封圈配合要求。密封圈内径应与电缆外径一致，保证密封和隔爆性能。B项内径过大电缆松动失去密封；C项内径过小无法套入且会损伤电缆；D项允差过大不符合隔爆要求。"},{"id":15,"type":"single","stem":"井下电气作业中，验电时应使用与电压等级相符的验电器，验电顺序应为","options":["先验低压后验高压","先验高压后验低压","先验近处后验远处","先验负荷侧后验电源侧"],"answer":[0],"explanation":"知识点：验电操作顺序。验电应先验低压后验高压，先验近处后验远处，先验负荷侧后验电源侧。B项先验高压顺序错误；C项先验近处正确但题干问的是电压等级顺序；D项先验负荷侧正确但同样不是电压等级顺序。"},{"id":16,"type":"single","stem":"矿用隔爆型电气设备中，隔爆结合面的粗糙度要求是","options":["不大于6.3μm","不大于3.2μm","不大于12.5μm","不大于1.6μm"],"answer":[0],"explanation":"知识点：隔爆结合面粗糙度要求。隔爆结合面粗糙度应不大于6.3μm以保证隔爆性能。B项3.2μm要求过高不必要；C项12.5μm过粗不能保证隔爆；D项1.6μm过于精细不符合实际要求。"},{"id":17,"type":"single","stem":"井下低压电网中，漏电保护装置的动作电阻值一般整定为","options":["1kΩ","10kΩ","100Ω","5kΩ"],"answer":[0],"explanation":"知识点：漏电保护整定值。井下低压漏电保护动作电阻值一般整定为1kΩ。B项10kΩ过大导致漏电时不能及时动作；C项100Ω过小可能误动；D项5kΩ不符合规定整定值。"},{"id":18,"type":"single","stem":"某井下变电所检修低压馈电开关，停电后验电、放电、挂牌，下一步应做的工作是","options":["在电源侧装设接地线","直接开始拆卸开关外壳","测量绝缘电阻确认无电","通知调度可以送电"],"answer":[0],"explanation":"知识点：停电检修安全操作程序。停电验电放电挂牌后应在电源侧装设接地线防止反送电。B项未装接地线直接拆卸存在反送电风险；C项测量绝缘电阻不能替代接地保护；D项检修未开始不能送电。"},{"id":19,"type":"single","stem":"井下电气设备隔爆外壳的紧固螺栓缺少弹簧垫圈时，正确的做法是","options":["补装规格相符的弹簧垫圈","用平垫圈代替弹簧垫圈","拧紧螺栓不加垫圈使用","用铜垫圈代替弹簧垫圈"],"answer":[0],"explanation":"知识点：隔爆外壳紧固件要求。紧固螺栓必须配弹簧垫圈防止松动，缺少时应补装规格相符的。B项平垫圈无防松功能；C项不加垫圈螺栓易松动失爆；D项铜垫圈不适用且可能产生火花。"},{"id":20,"type":"single","stem":"井下电气设备发生漏电故障后，在未查明原因前正确的做法是","options":["禁止强行送电并查找故障点","试送电一次判断能否恢复","提高漏电整定值后送电","甩掉漏电保护后送电"],"answer":[0],"explanation":"知识点：漏电故障处置原则。漏电故障未查明原因前禁止强行送电。B项试送电可能引发事故；C项提高整定值掩盖故障；D项甩掉保护严重违章。"},{"id":21,"type":"single","stem":"井下电气设备隔爆外壳的隔爆接合面涂凡士林的主要目的是什么","options":["防止接合面锈蚀并保持密封性能","降低外壳表面温升幅度","增强外壳整体机械强度","提高内部元件的绝缘水平"],"answer":[0],"explanation":"知识点：隔爆接合面维护。隔爆接合面涂凡士林可防锈并保持接合面间隙的隔爆性能，故A正确；表面温升由设备功率和散热决定，涂油无此作用，B错；机械强度由外壳材质和结构决定，C错；绝缘水平取决于内部绝缘材料和爬电距离，D错。"},{"id":22,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因前对该供电回路应采取的正确处置是","options":["试送一次观察是否再跳闸","将检漏保护短接后继续供电","拉开该回路隔离开关并挂牌","降低该回路负荷后恢复送电"],"answer":[2],"explanation":"知识点：漏电故障处置程序。检漏动作说明回路存在漏电隐患，须停电挂牌查明原因，故C正确；试送可能扩大事故，A错；短接检漏属严重违章，B错；漏电与负荷大小无关，降负荷不能消除隐患，D错。"},{"id":23,"type":"single","stem":"井下电气设备进行停电检修时，验电环节的正确操作对象是","options":["只需验放电侧各相导体","只需验电源侧各相导体","验电源侧和放电侧各相导体","验设备外壳与接地母线之间"],"answer":[2],"explanation":"知识点：停电检修验电范围。验电应确认电源侧和可能反送电的放电侧均无电，故C正确；只验一侧会漏掉反送电或残余电荷风险，A、B错；验外壳与接地之间属接地检查，不是验电内容，D错。"},{"id":24,"type":"single","stem":"井下低压馈电开关中，漏电闭锁功能与漏电保护功能的区别在于漏电闭锁作用于","options":["开关合闸之前阻止合闸","开关合闸之后切断故障","设备运行中降低动作值","故障消失后自动重合闸"],"answer":[0],"explanation":"知识点：漏电闭锁与漏电保护的区别。漏电闭锁在合闸前检测到绝缘低就闭锁，禁止合闸，故A正确；合闸后切断属漏电保护动作，B错；降低动作值不是闭锁功能，C错；自动重合闸与漏电闭锁无关，D错。"},{"id":25,"type":"single","stem":"井下电气设备隔爆外壳上紧固螺栓缺少弹簧垫圈时，正确的处理是","options":["用平垫圈代替后拧紧","加装规格相符的弹簧垫圈","用密封胶填充螺栓孔紧固","减少螺栓数量保持受力均匀"],"answer":[1],"explanation":"知识点：隔爆外壳紧固件要求。弹簧垫圈起防松作用，缺失必须补装同规格弹簧垫圈，故B正确；平垫圈无防松功能，A错；密封胶不能替代防松件，C错；减少螺栓会破坏外壳隔爆性能，D错。"},{"id":26,"type":"single","stem":"井下电缆连接时采用冷压接后，对接头绝缘恢复的规范做法是","options":["缠绕绝缘胶带后即可送电","缠绕胶带并做绝缘电阻测试","涂绝缘漆后直接包一层布带","套热缩管后不做绝缘测试"],"answer":[1],"explanation":"知识点：电缆接头绝缘恢复与检验。接头绝缘恢复后须测绝缘电阻合格才能送电，故B正确；仅缠胶带未测试无法确认绝缘合格，A错；绝缘漆加布带不能满足井下绝缘要求，C错；套热缩管后仍须测绝缘，D错。"},{"id":27,"type":"single","stem":"井下照明综合保护装置中，短路保护与漏电保护同时具备时，当发生漏电故障，装置应","options":["只发出漏电报警声光信号","同时切断短路和漏电回路","先漏电闭锁后切断供电","仅记录故障不切断供电"],"answer":[2],"explanation":"知识点：综合保护装置动作逻辑。漏电故障时装置先闭锁再切断该回路，故C正确；只报警不切断会留下触电隐患，A错；短路保护针对短路故障，不应同时动作，B错；只记录不切断不符合保护要求，D错。"},{"id":28,"type":"single","stem":"井下电气设备检修后送电前，测量绝缘电阻应使用","options":["万用表电阻档直接测量","兆欧表按规定电压测量","钳形电流表测量泄漏","接地电阻测试仪测量"],"answer":[1],"explanation":"知识点：绝缘电阻测量仪表。绝缘电阻须用对应电压等级的兆欧表测量，故B正确；万用表电阻档电压低、量程小，测不出合格绝缘，A错；钳形电流表测电流，C错；接地电阻测试仪测接地电阻，D错。"},{"id":29,"type":"single","stem":"井下电气设备运行中隔爆外壳表面出现裂纹但未穿透，正确的处置是","options":["打磨裂纹后继续使用","用焊条补焊后投入使用","立即停电更换该外壳","涂防锈漆后继续观察"],"answer":[2],"explanation":"知识点：隔爆外壳失效判断。外壳裂纹会破坏隔爆性能，必须停电更换，故C正确；打磨、补焊均无法恢复原隔爆结构，A、B错；涂漆掩盖裂纹继续使用属重大隐患，D错。"},{"id":30,"type":"single","stem":"井下电气作业中，接地网接地电阻的测试周期要求是","options":["每季度至少测试一次","每半年至少测试一次","每年至少测试一次","每两年至少测试一次"],"answer":[2],"explanation":"知识点：接地电阻测试周期。井下接地网接地电阻每年至少测定一次，故C正确；季度、半年、两年均不符合规定周期，A、B、D错。"},{"id":31,"type":"single","stem":"井下移动变电站低压侧漏电保护动作后，恢复送电前必须完成的工作是","options":["直接复位漏电保护试送电","查明漏电原因并处理合格","将漏电保护整定值调大","甩掉漏电保护后送电观察"],"answer":[1],"explanation":"知识点：漏电保护动作后处置。必须查明原因并处理合格后方可送电，故B正确；直接复位试送可能再次引发事故，A错；调大整定值属破坏保护，C错；甩掉保护送电严重违章，D错。"},{"id":32,"type":"multi","stem":"井下电气设备隔爆性能检查中，下列属于必须检查的隔爆要素有哪些","options":["隔爆接合面间隙是否符合规定","外壳紧固螺栓是否齐全紧固","电缆引入装置的密封圈是否完好","设备内部绝缘材料颜色是否一致","外壳表面防腐漆是否涂刷均匀"],"answer":[0,1,2],"explanation":"知识点：隔爆性能检查要素。隔爆接合面间隙、紧固螺栓、电缆引入密封圈均直接关系隔爆性能，故A、B、C正确；绝缘材料颜色与隔爆无关，D错；防腐漆均匀与否不影响隔爆性能，E错。"},{"id":33,"type":"single","stem":"井下电气设备隔爆外壳的隔爆接合面涂油时，应选用下列哪种油脂","options":["钙基润滑脂","凡士林或防锈油","二硫化钼锂基脂","工业齿轮油"],"answer":[1],"explanation":"知识点：隔爆接合面防锈处理。隔爆接合面需涂凡士林或防锈油以防止锈蚀，且不影响隔爆性能。钙基润滑脂耐温低且易流失，不能用于接合面防锈；二硫化钼锂基脂含固体颗粒，会增大接合面间隙；工业齿轮油黏度大、易积尘，不符合接合面防锈要求。"},{"id":34,"type":"single","stem":"井下检漏保护装置动作后，在恢复送电前应先做的工作是","options":["直接复位后送电","查明漏电原因并处理","将检漏继电器退出运行","提高整定值后试送电"],"answer":[1],"explanation":"知识点：漏电闭锁后的处置程序。检漏装置动作说明电网存在漏电，必须先查明并处理漏电故障，否则送电会造成人身触电或引爆瓦斯。直接复位送电属带故障强送；退出检漏属甩保护运行；提高整定值会降低保护灵敏度，均为错误做法。"},{"id":35,"type":"single","stem":"井下电气设备用螺栓紧固隔爆外壳时，弹簧垫圈的正确安装位置是","options":["垫在螺母与外壳之间","垫在螺栓头与外壳之间","螺母侧和螺栓头侧各垫一个","只垫在螺栓头侧且压平"],"answer":[0],"explanation":"知识点：隔爆外壳紧固件安装要求。弹簧垫圈应装在螺母侧，起防松作用，保证紧固可靠。垫在螺栓头侧起不到防松作用；两侧各垫一个不符合装配规范且可能影响紧固力矩；压平弹簧垫圈会使其失去弹性防松功能。"},{"id":36,"type":"single","stem":"井下供电系统中，对每台电气设备单独敷设的接地芯线，其正确连接方式是","options":["与设备外壳并联后接局部接地极","与主接地极直接串联连接","与电缆金属护套合并使用","接入相邻设备的接地端子"],"answer":[0],"explanation":"知识点：保护接地连接方式。每台设备的接地芯线应并联接入接地网或局部接地极，保证接地可靠。串联连接会导致一处断开使后续设备失去接地；与金属护套合并会因护套连接不可靠而失效；接入相邻设备端子属于串联接地，同样存在断线风险。"},{"id":37,"type":"single","stem":"井下选用矿用橡套电缆时，其主芯线截面为16mm²，接地芯线截面应不小于","options":["4mm²","6mm²","10mm²","16mm²"],"answer":[2],"explanation":"知识点：橡套电缆接地芯线截面配合。主芯线为16mm²时，接地芯线截面应不小于10mm²，以保证接地故障电流可靠流通。4mm²和6mm²偏小，不能满足接地保护要求；与主芯线等截面虽安全但不符合经济选型规定。"},{"id":38,"type":"single","stem":"井下电气设备运行中，隔爆外壳上观察窗玻璃出现裂纹但未脱落，正确的处置是","options":["用密封胶封堵裂纹后继续运行","停电更换观察窗玻璃","降低负荷继续运行观察","在裂纹处加贴透明胶带"],"answer":[1],"explanation":"知识点：隔爆外壳完整性要求。观察窗玻璃裂纹即使未脱落也破坏了隔爆性能，必须停电更换。密封胶封堵不能恢复隔爆强度；降低负荷不能消除失爆风险；贴胶带属临时掩盖，均不能恢复隔爆性能。"},{"id":39,"type":"single","stem":"井下电气设备停电检修时，验电、放电、挂接地线的正确顺序是","options":["放电、验电、挂接地线","验电、放电、挂接地线","挂接地线、验电、放电","验电、挂接地线、放电"],"answer":[1],"explanation":"知识点：停电检修安全操作程序。必须先验电确认无电，再对电缆或电容器放电，最后挂接地线，顺序不可颠倒。先放电未验电可能误判带电；先挂接地线可能带电挂接造成事故；先挂接地线再放电则放电电流经接地线，顺序错误。"},{"id":40,"type":"single","stem":"井下移动变电站低压侧馈电开关的漏电闭锁整定值，下列做法正确的是","options":["按设备额定电压对应值整定","随意调高以提高供电可靠性","退出漏电闭锁功能","按最大负荷电流整定"],"answer":[0],"explanation":"知识点：漏电闭锁整定原则。漏电闭锁值应按设备额定电压对应的规定值整定，保证绝缘降低时可靠闭锁。调高整定值会降低灵敏度；退出功能属甩保护；按负荷电流整定混淆了过流与漏电保护概念。"},{"id":41,"type":"single","stem":"井下照明信号综合保护装置中，短路保护与漏电保护的关系是","options":["两者共用同一整定值","短路保护动作后漏电保护自动闭锁","漏电保护动作后短路保护仍可投入","两者相互独立分别整定"],"answer":[3],"explanation":"知识点：综合保护装置各保护功能关系。短路保护与漏电保护是相互独立的保护功能，分别整定、互不干扰。共用整定值会顾此失彼；短路动作后漏电保护不应自动闭锁；漏电动作后短路保护是否投入取决于装置逻辑，不能一概而论。"},{"id":42,"type":"single","stem":"井下某掘进工作面局部通风机突然停风，瓦斯检查工发现停风区瓦斯浓度已达1.5%，此时电气设备的正确处置是","options":["立即切断停风区电气设备电源","等待瓦斯自行降低后恢复送电","保持设备运行加强通风","仅停局部通风机继续其他作业"],"answer":[0],"explanation":"知识点：停风区瓦斯超限时的电气处置。停风区瓦斯浓度达到1.5%时，必须立即切断该区域电气设备电源，防止电火花引爆瓦斯。等待自行降低属延误处置；保持设备运行会因电火花引发爆炸；仅停局部通风机不能切断电气设备电源，风险依然存在。"},{"id":43,"type":"single","stem":"井下电气设备隔爆外壳的隔爆面不得有影响隔爆性能的缺陷，下列哪种情况必须停止使用该设备","options":["隔爆面有轻微锈迹但擦除后表面光滑","隔爆面局部有长度8mm的机械划痕","隔爆面涂有薄层防锈油脂","隔爆面有轻微氧化色但无凹坑"],"answer":[1],"explanation":"知识点：隔爆面损伤判定。隔爆面的划痕若达到一定长度和深度会形成火焰通路，影响隔爆性能，必须停止使用并上井处理。轻微锈迹擦除后光滑不影响隔爆性能；涂防锈油脂是允许的维护措施；氧化色无凹坑不影响隔爆性能。"},{"id":44,"type":"single","stem":"井下电气设备防爆检查中，用便携式甲烷检测仪在设备外壳附近检测瓦斯浓度，下列读数中允许继续作业的是","options":["甲烷浓度0.8%","甲烷浓度1.2%","甲烷浓度1.5%","甲烷浓度2.0%"],"answer":[0],"explanation":"知识点：井下电气作业瓦斯浓度限值。井下电气设备附近瓦斯浓度低于1.0%时允许作业，达到1.0%及以上必须停止电气作业并切断电源。0.8%低于1.0%可以作业；1.2%、1.5%、2.0%均超过限值，必须停电撤人。"},{"id":45,"type":"single","stem":"井下电缆连接时，对电缆芯线连接的要求，下列做法中正确的是","options":["铜芯与铝芯电缆直接压接后缠绝缘带","同材质芯线采用冷压连接并做好绝缘密封","芯线绞接后仅用绝缘胶布缠绕三层","芯线用螺栓压接后裸露部分涂防锈漆"],"answer":[1],"explanation":"知识点：井下电缆芯线连接工艺。井下电缆芯线连接必须采用同材质、冷压或焊接等可靠方式，并做好绝缘密封，防止潮气和瓦斯侵入。铜铝直接连接会产生电化学腐蚀；绞接加胶布强度不足且不密封；螺栓压接后涂漆不能代替绝缘密封。"},{"id":46,"type":"single","stem":"井下某低压馈电开关送电后频繁跳闸，现场电钳工处理时下列做法正确的是","options":["将漏电保护整定值调大后继续送电","断开所有负荷后逐路试送查找故障支路","将漏电闭锁短接后强制送电观察","更换更大额定电流的熔断器后送电"],"answer":[1],"explanation":"知识点：低压馈电开关跳闸排查程序。正确做法是断开全部负荷，逐路试送，找出绝缘损坏或漏电的支路。调大漏电整定值是甩保护；短接漏电闭锁是严重违章；换大熔断器不能解决漏电跳闸且破坏保护配合。"},{"id":47,"type":"single","stem":"井下电气设备进行检修需要停电时，验电环节的正确操作是","options":["用低压验电笔在设备外壳上验电确认无电","在停电开关的负荷侧用同电压等级验电器验电","用万用表在开关电源侧测量确认无电压","观察开关分闸指示灯熄灭后即可确认无电"],"answer":[1],"explanation":"知识点：停电检修验电程序。验电应在检修设备的进出线两侧、用与电压等级相符的验电器进行，重点在负荷侧。验电笔测外壳不能判断线路是否带电；在电源侧验电不能确认负荷侧无电；指示灯可能误指示，不能代替验电。"},{"id":48,"type":"single","stem":"井下电气设备接地保护中，关于局部接地极的设置，下列说法正确的是","options":["局部接地极可用直径不小于35mm、长度不小于1.5m的钢管","局部接地极可设置在巷道水沟中且必须垂直插入底板","连接导线与接地极可用螺栓连接后涂漆防锈","接地极埋深不小于0.3m即可满足要求"],"answer":[0],"explanation":"知识点：局部接地极规格要求。局部接地极用直径不小于35mm、长度不小于1.5m的钢管，这是规程规定的规格。接地极应垂直埋入底板而非水沟；接地连接必须焊接或压接，涂漆会增大接触电阻；接地极埋深有明确要求，0.3m不满足规定。"},{"id":49,"type":"single","stem":"井下防爆电气设备隔爆接合面的紧固螺栓，下列使用方式正确的是","options":["用弹簧垫圈加平垫圈紧固并留有防松措施","缺少一个螺栓时用铁丝绑扎固定外壳","用加长螺栓穿透外壳固定内部元件","螺栓拧紧后露出螺母三扣以上螺纹"],"answer":[0],"explanation":"知识点：隔爆外壳紧固螺栓要求。隔爆外壳紧固螺栓必须齐全、拧紧，应有防松措施如弹簧垫圈。缺螺栓用铁丝绑扎会破坏隔爆性能；加长螺栓穿透外壳可能形成泄漏通路；螺栓露出螺母的螺纹扣数一般为1至3扣，露出过多说明螺栓过长或未拧紧到位。"},{"id":50,"type":"single","stem":"井下电气作业人员发现有人触电时，首先应当采取的措施是","options":["立即用手将触电者拉离带电体","迅速切断电源或用绝缘物使触电者脱离带电体","先对触电者进行人工呼吸再切断电源","立即向矿调度室汇报后再处理"],"answer":[1],"explanation":"知识点：触电急救第一步。发现有人触电，首要措施是迅速切断电源或用干燥绝缘物使触电者脱离带电体，然后进行急救。直接用手拉会造成施救者触电；先急救再断电会延误且危险；先汇报再处理会错过最佳抢救时机。"},{"id":51,"type":"single","stem":"井下电气设备防爆标志ExdI中，字母d表示的含义是","options":["增安型","隔爆型","本质安全型","正压型"],"answer":[1],"explanation":"知识点：防爆型式标志含义。ExdI中d代表隔爆型，I代表煤矿井下用电气设备。增安型用e表示；本质安全型用i表示；正压型用p表示。"},{"id":52,"type":"single","stem":"井下电气设备检修完成后送电前，必须完成的程序是","options":["清点工具、拆除接地线、确认无人在设备上工作后送电","直接合闸试送电，观察设备运行是否正常","通知调度后即可送电，无需其他确认","测量绝缘电阻后立即送电，不需拆除接地线"],"answer":[0],"explanation":"知识点：检修后送电程序。送电前必须清点工具材料、拆除临时接地线、确认设备上无人工作、恢复防护装置，然后按程序送电。直接合闸试送可能造成人员伤亡；仅通知调度不够；接地线未拆除就送电会造成短路。"},{"id":53,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面涂防锈油时，正确做法是涂在哪个部位","options":["隔爆结合面全部表面","隔爆结合面外侧非配合面","隔爆结合面内侧非配合面","隔爆结合面及其附近螺栓螺纹"],"answer":[1],"explanation":"知识点：隔爆结合面防锈处理要求。隔爆结合面本身不得涂油，涂油会改变间隙、影响隔爆性能，只能在外侧非配合面涂防锈油；涂全部表面会破坏隔爆间隙；内侧非配合面涂油无意义且可能污染内部；涂螺栓螺纹不能替代结合面防锈且油脂可能渗入结合面。"},{"id":54,"type":"single","stem":"井下检漏保护装置动作后，在恢复送电前必须完成的确认工作是","options":["测量电网绝缘电阻并做好记录","将检漏装置退出运行后试送","对电网进行人工放电后试送","拉开隔离开关等待五分钟"],"answer":[0],"explanation":"知识点：漏电闭锁后恢复送电程序。检漏装置动作说明绝缘可能损坏，必须测绝缘确认合格；退出检漏装置送电属于甩保护；人工放电不能判断绝缘是否恢复；拉开隔离开关等待只是延时，不能确认绝缘状态。"},{"id":55,"type":"single","stem":"井下电气设备运行中闻到焦糊味且外壳温度明显升高，现场人员首先应当","options":["打开外壳检查内部发热点","切断该设备电源并报告","降低负荷继续观察运行","用灭火器对外壳降温处理"],"answer":[1],"explanation":"知识点：设备异常温升的应急处置。焦糊味加温升说明可能已过热或绝缘损坏，首先必须停电并报告；带电开盖检查违反停电检修原则；降负荷继续运行会扩大故障；对外壳降温不切断电源，热源仍在，还可能造成外壳变形失爆。"},{"id":56,"type":"single","stem":"井下低压馈电开关中，漏电闭锁与漏电保护在功能上的区别是","options":["漏电闭锁在送电前检测绝缘并闭锁合闸，漏电保护在运行中检测并跳闸","漏电闭锁在运行中跳闸，漏电保护在送电前闭锁合闸","漏电闭锁只检测电缆，漏电保护只检测电动机绕组","漏电闭锁动作后自动重合闸，漏电保护动作后不重合"],"answer":[0],"explanation":"知识点：漏电闭锁与漏电保护的区分。闭锁是在合闸前监测绝缘电阻，不合格则闭锁不能合闸；保护是在运行中监测到漏电后跳闸。选项B把两者时序颠倒；选项C把检测对象限定错；选项D混淆了是否重合闸与两种功能的定义。"},{"id":57,"type":"single","stem":"井下用摇表测量1140V电缆绝缘电阻前，必须完成的操作是","options":["将电缆两端导体短接放电并确认停电","将摇表转速先升至额定后再接线","把电缆另一端接在开关负荷侧","测量时同时用手接触导体读取数值"],"answer":[0],"explanation":"知识点：绝缘电阻测量安全准备。电缆停电后可能存有残余电荷，必须短接放电并确认停电；摇表应先接线后摇动，不是先升至额定再接线；另一端接负荷侧会使读数受设备影响；测量时手触导体将造成触电危险。"},{"id":58,"type":"single","stem":"井下隔爆电气设备安装时，设备外壳接地端子与接地母线连接的正确要求是","options":["用铜编织线压接并可靠固定","用铁丝缠绕拧紧后刷漆","用铝排点焊在外壳上","用普通螺栓加弹簧垫压紧导线"],"answer":[0],"explanation":"知识点：隔爆设备接地连接要求。接地连接应使用铜编织线或铜芯导线压接牢固；铁丝缠绕、铝排点焊均不符合连接可靠性要求；普通螺栓压紧导线缺少专用接地螺栓和防松措施，接触电阻不能保证。"},{"id":59,"type":"single","stem":"井下电气设备检修需要停高压开关时，验电的正确部位是","options":["开关负荷侧和电源侧分别验电","只在开关负荷侧验电","只在开关电源侧验电","在开关外壳上验电确认无电"],"answer":[0],"explanation":"知识点：高压停电检修验电范围。必须对可能来电的各侧分别验电，负荷侧和电源侧都要验；只验一侧可能漏掉反送电；外壳验电不能代替导体验电，无法确认内部是否带电。"},{"id":60,"type":"single","stem":"井下电缆与电气设备连接时，密封圈内径与电缆外径的配合要求是","options":["密封圈内径与电缆外径的差值不大于1mm","密封圈内径应比电缆外径大2mm以上","密封圈内径应比电缆外径小1mm以便压紧","密封圈内径与电缆外径相同即可不考核差值"],"answer":[0],"explanation":"知识点：电缆引入装置密封圈配合要求。密封圈内径与电缆外径差过大不能有效密封，通常要求差值不大于1mm；大2mm以上会漏气失爆；小1mm会损伤电缆绝缘且装配困难；相同不考核差值不符合标准对公差的控制要求。"},{"id":61,"type":"single","stem":"井下使用中的隔爆型电动机，其隔爆结合面出现轻微锈蚀但未超过规定间隙，正确处理方式是","options":["清除锈蚀并涂防锈油后继续使用","用砂纸打磨结合面使其光亮","直接继续使用并加强温度监测","用油漆涂覆结合面防止再锈"],"answer":[0],"explanation":"知识点：隔爆结合面锈蚀处理。轻微锈蚀应清除后涂防锈油，并确认间隙仍符合规定；砂纸打磨会改变结合面平面度和间隙；直接使用不处理会加剧锈蚀；油漆涂覆会改变隔爆间隙并影响隔爆性能。"},{"id":62,"type":"single","stem":"井下电气作业中，操作高压开关手动合闸时，操作人员正确的站位和防护是","options":["站在开关侧面并戴绝缘手套穿绝缘靴","站在开关正面并戴防护眼镜","站在开关侧面并戴普通线手套","站在开关背面并穿防静电工作服"],"answer":[0],"explanation":"知识点：高压开关手动操作安全要求。操作高压开关应站在侧面，防止电弧正面伤人，并戴绝缘手套穿绝缘靴；正面站位易受电弧伤害；普通线手套无绝缘性能；背面站位不能有效观察开关状态且防静电服不防电弧。"},{"id":63,"type":"single","stem":"井下电气设备隔爆外壳的隔爆接合面严禁涂油漆，其原因是油漆会使接合面的间隙发生变化，从而可能造成哪种后果？","options":["隔爆面锈蚀速度加快导致外壳强度下降","爆炸火焰从接合面间隙向外传播失去隔爆作用","接合面导电性能变差引发漏电保护误动","外壳内部潮气无法排出导致绝缘受潮"],"answer":[1],"explanation":"知识点：隔爆接合面的间隙是隔爆性能的关键参数，火焰通过狭窄间隙时被冷却熄灭。正确项：涂漆改变间隙尺寸，火焰可能不被充分冷却而传出，失去隔爆作用。错误项：锈蚀影响的是表面状态和强度，不是涂漆直接导致的间隙失效主因；接合面不承担导电功能，与漏电保护无关；隔爆外壳本身不靠接合面排潮。"},{"id":64,"type":"single","stem":"井下低压检漏保护装置在运行中出现绝缘电阻低于整定值但未达到动作值时，正确的处理方式是？","options":["立即手动断开该支路电源并挂牌","暂不动作，由值班电工加强监视并查找原因","将检漏装置整定值调低使其不动作","退出检漏保护装置待检修时再恢复"],"answer":[1],"explanation":"知识点：检漏保护具有分级动作特性，未达动作值时应加强监视和排查而非盲目停电或调整定值。正确项：低于整定值但未达动作值时按运行规程监视查因。错误项：立即断电会造成不必要的停产，且未达动作值说明尚未危及安全；调低定值会削弱保护功能属于擅自改动保护参数；退出保护装置更是严重违章，会使漏电失去保护。"},{"id":65,"type":"single","stem":"井下使用的橡套电缆在连接时，若采用冷压连接后再硫化热补，其主要目的是保证连接处的？","options":["抗拉强度不低于原电缆","绝缘性能和密封性能满足井下要求","导体电阻小于原电缆导体","电缆外径与原电缆一致"],"answer":[1],"explanation":"知识点：井下电缆连接必须恢复绝缘和密封，防止潮气侵入和漏电。正确项：硫化热补使连接处绝缘和密封达到要求。错误项：抗拉强度不是热补主要目的；导体电阻不可能小于原电缆；外径一致只是外观，不是核心要求。"},{"id":66,"type":"single","stem":"井下电气设备中，隔爆型电气设备的标志是？","options":["ExdI","ExeI","ExiI","ExdII"],"answer":[0],"explanation":"知识点：煤矿井下隔爆型标志为ExdI，其中I表示煤矿用电气设备。正确项：ExdI是隔爆型煤矿用标志。错误项：ExeI是增安型；ExiI是本安型；ExdII是工厂用隔爆型，不适用于煤矿井下。"},{"id":67,"type":"single","stem":"井下电气作业人员在进行电气设备检修时，若发现隔爆外壳的隔爆接合面有轻微锈蚀，正确的处理方法是？","options":["用砂纸打磨除锈后涂防锈油","用棉纱擦拭干净后直接安装","用刮刀刮除锈层后涂油漆","用钢丝刷清理后涂润滑脂"],"answer":[0],"explanation":"知识点：隔爆接合面除锈应使用砂纸或专用工具，除锈后涂防锈油，且不能涂油漆。正确项：砂纸打磨除锈后涂防锈油可恢复隔爆性能。错误项：仅擦拭不能除锈；刮刀会损伤接合面精度；涂油漆会改变间隙且钢丝刷会划伤接合面。"},{"id":68,"type":"single","stem":"井下供电系统中，过流保护装置的动作电流整定值应根据什么来确定？","options":["被保护线路的最大负荷电流","被保护线路的最小短路电流","被保护线路的额定电压","被保护线路的绝缘电阻"],"answer":[0],"explanation":"知识点：过流保护整定值应躲过最大负荷电流，同时保证最小短路电流时能可靠动作。正确项：按最大负荷电流整定可避免正常运行时误动。错误项：最小短路电流用于校验灵敏度，不是整定值依据；额定电压和绝缘电阻与过流整定无直接关系。"},{"id":69,"type":"single","stem":"井下电气设备运行中，若发现电动机声音异常、温度升高且电流表指示增大，首先应采取的措施是？","options":["立即停机并断开电源检查","继续运行观察一段时间","降低负荷继续运行","加大冷却风量继续运行"],"answer":[0],"explanation":"知识点：电动机异常声响、温升和电流增大可能是过载、缺相或机械故障，应立即停机检查。正确项：立即停机断电可防止故障扩大。错误项：继续运行会烧毁电机；降低负荷不能消除故障；加大冷却只是治标不治本。"},{"id":70,"type":"single","stem":"井下电气设备安装时，电缆与设备连接处的密封圈内径应与电缆外径匹配，若密封圈内径过大，可能导致的后果是？","options":["电缆拉脱力增大","失去隔爆密封作用","电缆载流量下降","接地电阻增大"],"answer":[1],"explanation":"知识点：密封圈内径必须与电缆外径紧密配合，过大则无法密封，失去隔爆性能。正确项：内径过大会使密封失效。错误项：拉脱力与密封圈内径无关；载流量取决于导体截面；接地电阻与密封圈无关。"},{"id":71,"type":"single","stem":"井下进行电气设备检修时，若需要打开隔爆外壳，在停电后还必须进行的操作是？","options":["验电、放电并挂接地线","直接打开外壳检查","测量绝缘电阻后打开","通知调度后打开"],"answer":[0],"explanation":"知识点：打开隔爆外壳前必须执行停电、验电、放电、挂接地线等安全措施。正确项：验电放电挂接地线是必要步骤。错误项：直接打开可能带电；测绝缘不能代替验电放电；通知调度只是汇报，不能替代安全操作。"},{"id":72,"type":"multi","stem":"井下电气设备隔爆性能检查中，下列哪些项目属于必须检查的内容？","options":["隔爆接合面的间隙和表面粗糙度","隔爆外壳的紧固螺栓是否齐全拧紧","隔爆接合面是否涂有油漆","电缆引入装置的密封圈是否完好","设备外壳的接地端子是否锈蚀"],"answer":[0,1,3],"explanation":"知识点：隔爆性能检查包括接合面间隙、粗糙度、紧固螺栓、密封圈等。正确项：接合面间隙和粗糙度、紧固螺栓、密封圈均影响隔爆性能。错误项：接合面涂油漆是禁止的，检查中应确认未涂油漆，但“是否涂有油漆”不是必须检查项目而是违规项；接地端子锈蚀属于接地检查，不是隔爆性能检查内容。"},{"id":73,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面若有轻微锈蚀，正确的处理方式是","options":["用砂纸打磨至露出金属光泽后涂防锈油","用棉纱擦拭干净后直接复用","用刮刀刮除锈迹再测量间隙","用酸洗除锈后检查间隙合格即可"],"answer":[2],"explanation":"知识点：隔爆结合面锈蚀处理须保证间隙不超标。正确项对：刮除锈迹后必须测量结合面间隙是否仍在允许范围内，锈蚀会改变有效间隙。A项错：砂纸打磨会改变结合面粗糙度和间隙，涂油也影响隔爆性能。B项错：仅擦拭无法去除深层锈蚀，间隙可能已超标。D项错：酸洗会腐蚀金属改变结合面尺寸。"},{"id":74,"type":"single","stem":"井下检漏继电器动作后，在未查明原因前正确的做法是","options":["试送电一次判断是否误动作","将检漏继电器退出后送电","保持闭锁状态查明并排除故障","调整整定值后恢复送电"],"answer":[2],"explanation":"知识点：检漏继电器动作后须查明原因方可送电。正确项对：保持闭锁查明排除故障才能确保漏电隐患消除。A项错：试送电可能造成漏电事故扩大。B项错：退出检漏属严重违章。D项错：调整整定值掩盖了真实漏电故障。"},{"id":75,"type":"single","stem":"井下电气设备运行中，电动机外壳温度突然升高且伴有焦糊味，首先应","options":["继续观察温度变化趋势","断电停机检查原因","打开外壳通风散热","降低负荷维持运行"],"answer":[1],"explanation":"知识点：电动机过热伴焦糊味是绕组绝缘故障征兆。正确项对：应立即断电停机，防止绕组烧毁或引发火灾。A项错：继续观察会延误处理造成设备损坏。C项错：带电打开外壳违反安全规定且不能解决根本问题。D项错：降低负荷不能消除绝缘故障隐患。"},{"id":76,"type":"single","stem":"井下使用中的防爆电气设备，隔爆外壳上的紧固螺栓要求是","options":["螺栓齐全且弹簧垫圈压平","螺栓齐全且紧固到位","缺少个别螺栓可用铁丝绑扎固定","螺栓可少装但须加密封胶"],"answer":[1],"explanation":"知识点：隔爆外壳紧固螺栓须齐全并紧固到位以保持隔爆性能。正确项对：齐全且紧固到位才能保证隔爆面压紧。A项错：弹簧垫圈压平与否不是判断标准，关键是齐全紧固。C项错：铁丝绑扎不能代替螺栓紧固。D项错：少装螺栓加密封胶不能保证隔爆。"},{"id":77,"type":"single","stem":"井下电气设备接地网上任一保护接地点的接地电阻值，其检测周期要求是","options":["每季度至少测定一次","每半年至少测定一次","每年至少测定一次","每两年至少测定一次"],"answer":[0],"explanation":"知识点：井下接地网接地电阻每季度至少测定一次。正确项对：季度测定可及时发现接地电阻变化。B项错：半年周期过长。C项错：一年周期过长。D项错：两年远超规定周期。"},{"id":78,"type":"single","stem":"井下电气设备进行绝缘电阻测定时，发现绝缘电阻值较上次记录明显下降但仍在合格范围内，正确处理是","options":["视为合格继续运行并加强监视","立即停止运行更换设备","烘干处理后恢复运行","缩短测定周期跟踪变化趋势"],"answer":[3],"explanation":"知识点：绝缘电阻下降趋势是设备受潮或老化的早期信号。正确项对：缩短测定周期跟踪趋势可及时发现恶化。A项错：仅监视不缩短周期会漏过快速恶化。B项错：仍在合格范围不需立即更换。C项错：未确认受潮就烘干处理缺乏依据。"},{"id":79,"type":"single","stem":"井下局部通风机电源与掘进工作面电气设备电源的正确关系是","options":["可共用同一台馈电开关","风机电源须取自掘进工作面电源","风机须采用选择性漏电保护","风机电源须独立并实行风电闭锁"],"answer":[3],"explanation":"知识点：局部通风机须独立供电并实行风电闭锁。正确项对：独立电源保证停风时风机不断电，风电闭锁保证停风停掘进电源。A项错：共用开关无法保证独立供电。B项错：取自工作面电源失去独立性。C项错：选择性漏电保护不是风机供电的核心要求。"},{"id":80,"type":"single","stem":"井下电气设备检修中需要带电搬迁时，必须满足的条件是","options":["搬迁前切断电源并验电放电","搬迁中保持设备与电缆连接","经调度批准后可带电搬迁","在瓦斯浓度低于规定值时搬迁"],"answer":[0],"explanation":"知识点：搬迁电气设备必须先停电。正确项对：切断电源并验电放电是搬迁前必须完成的安全步骤。B项错：搬迁中保持连接是带电作业隐患。C项错：带电搬迁本身不允许，批准也不能违反。D项错：瓦斯浓度合格不代表可以带电搬迁。"},{"id":81,"type":"single","stem":"井下电气设备隔爆外壳透明件（观察窗）损坏后的正确处理是","options":["用普通玻璃临时替换后运行","用相同规格的隔爆透明件更换","用金属板封堵后继续运行","用环氧树脂粘补后运行"],"answer":[1],"explanation":"知识点：隔爆透明件须用规定材质和规格的配件更换。正确项对：相同规格隔爆透明件能保证隔爆性能。A项错：普通玻璃强度不够不能隔爆。C项错：金属板封堵改变设备结构影响观察和隔爆。D项错：粘补不能恢复隔爆性能。"},{"id":82,"type":"single","stem":"井下电气设备隔爆外壳的隔爆接合面涂防锈油时，正确的做法是涂在什么部位","options":["接合面的外缘和螺栓孔周围","整个隔爆接合面并擦净多余油","接合面内侧靠近腔体一侧","外壳非接合面的外表面"],"answer":[0],"explanation":"知识点：隔爆接合面不得涂油以免影响隔爆性能，只能在外缘防锈。正确项涂外缘和螺栓孔周围可防锈又不影响隔爆间隙；涂整个接合面会改变间隙、积尘；涂内侧靠近腔体会污染腔内并影响隔爆；涂外表面与接合面防锈无关。"},{"id":83,"type":"single","stem":"井下检漏继电器每天应进行的试验是","options":["用试验按钮做一次跳闸试验","测量电网对地绝缘电阻数值","校对电流互感器变比","检查接地极接地电阻"],"answer":[0],"explanation":"知识点：检漏继电器每班或每天需用试验按钮做跳闸试验，确认动作可靠。正确项即日常跳闸试验；测绝缘电阻是定期检测项目；校电流互感器变比属检修校验；测接地电阻属定期测量，均非每日试验内容。"},{"id":84,"type":"single","stem":"井下电气设备检修后送电前，确认无人作业并撤除接地线的正确顺序是","options":["先拆除接地线，再检查确认无人后送电","先检查确认无人，再拆除接地线后送电","先送电试运行，再拆除接地线","先拆除接地线并送电，最后检查现场"],"answer":[1],"explanation":"知识点：送电前必须确认无人作业、拆除接地线并恢复防护，顺序不能颠倒。正确项先确认无人再拆接地线符合程序；先拆接地线再检查会使线路失去保护；先送电再拆接地线属带电拆接地线，极危险；先拆线送电最后检查颠倒顺序，遗漏确认环节。"},{"id":85,"type":"single","stem":"矿用隔爆型电气设备隔爆接合面的最小宽度和最大间隙，主要取决于","options":["设备额定电压和隔爆类别等级","设备额定电流和导线截面","设备安装地点和巷道断面","设备外壳材质和重量"],"answer":[0],"explanation":"知识点：隔爆接合面参数由电气设备的隔爆类别、级别和温度组别等决定。正确项额定电压和隔爆类别等级是决定因素；额定电流和导线截面影响载流而非隔爆间隙；安装地点和巷道断面属使用环境；外壳材质和重量不是决定接合面尺寸的核心依据。"},{"id":86,"type":"single","stem":"井下电气设备进行保护接地时，接地网上任一保护接地点的接地电阻值不得超过","options":["1Ω","2Ω","4Ω","10Ω"],"answer":[1],"explanation":"知识点：井下保护接地网任一保护接地点的接地电阻不得超过2Ω。正确项2Ω符合规定；1Ω要求过严，不是该处规定值；4Ω是地面部分电气设备接地要求的常见值，易混；10Ω过大，不能保证保护接地效果。"},{"id":87,"type":"single","stem":"井下电缆与电气设备连接时，采用压紧螺母式引入装置的正确做法是","options":["密封圈内径与电缆外径配合，压紧后电缆不松动","密封圈内径大于电缆外径，用棉纱填塞压紧","密封圈内径小于电缆外径，强行压入固定","不用密封圈，直接用压紧螺母压紧电缆"],"answer":[0],"explanation":"知识点：引入装置密封圈内径应与电缆外径匹配，压紧后电缆不松动且密封良好。正确项配合适当符合要求；内径过大用棉纱填塞不密封；内径过小强行压入会损伤电缆和密封圈；不用密封圈失去隔爆密封作用。"},{"id":88,"type":"single","stem":"井下电气设备隔爆外壳上的观察窗玻璃，其安装要求是","options":["采用足够强度的玻璃并用密封垫和压板固定","采用普通玻璃并用胶粘剂粘接固定","采用钢化玻璃直接卡在窗口槽内","采用有机玻璃用螺钉从外侧压紧"],"answer":[0],"explanation":"知识点：隔爆观察窗须用规定强度玻璃，通过密封垫和压板可靠固定以保持隔爆性能。正确项符合要求；普通玻璃加胶粘强度不足且不可靠；钢化玻璃直接卡槽内无密封压紧不可靠；有机玻璃强度和耐热不足，外侧螺钉压紧也不能保证隔爆。"},{"id":89,"type":"single","stem":"井下电气设备运行中出现外壳温度明显升高且有焦糊味，正确的下一步处置是","options":["立即停电检查，查明原因并处理后再送电","继续运行并加强通风降温观察","降低负荷继续运行至检修班处理","打开外壳散热后继续运行"],"answer":[0],"explanation":"知识点：设备异常温升伴焦糊味可能内部故障，应立即停电检查。正确项立即停电检查符合异常处置；继续运行可能扩大故障；降负荷运行仍带故障；打开外壳散热会破坏隔爆且不能消除故障。"},{"id":90,"type":"multi","stem":"井下电气设备检修中，下列属于必须执行的安全措施有","options":["停电并验电确认无电","装设接地线并悬挂警示牌","检修前检查瓦斯浓度合格","约时送电以便掌握进度","用湿布擦拭带电设备外壳"],"answer":[0,1,2],"explanation":"知识点：井下电气检修必须停电、验电、放电、装设接地线、挂牌并检查瓦斯。前三项均为必须执行的安全措施；约时送电是严禁的做法，容易造成误送电伤人；用湿布擦拭带电设备外壳严重违章。"},{"id":91,"type":"single","stem":"井下电气设备检修后送电前，测量电缆绝缘电阻合格，但送电时开关立即跳闸，最可能的原因是","options":["电缆相序接反导致相间短路","绝缘电阻表电压等级选低","漏电闭锁或保护整定值未复归","接地芯线截面偏小"],"answer":[2],"explanation":"知识点：检修后送电程序与漏电闭锁复位。正确项：检修时保护装置动作后未复归或整定值未恢复，送电即被闭锁跳闸。错误项：相序接反不会立即造成短路跳闸；绝缘表电压等级低只影响测量结果不影响送电；接地芯线截面偏小不引起送电瞬间跳闸。"},{"id":92,"type":"single","stem":"井下低压馈电开关的漏电保护装置，其动作电阻整定值应保证在电网绝缘电阻降到多少时可靠动作","options":["1140V系统低于40kΩ、660V系统低于11kΩ","1140V系统低于20kΩ、660V系统低于7kΩ","1140V系统低于60kΩ、660V系统低于30kΩ","1140V系统低于80kΩ、660V系统低于40kΩ"],"answer":[0],"explanation":"知识点：井下低压漏电保护动作电阻整定值。正确项：1140V系统低于40kΩ、660V系统低于11kΩ时漏电保护应可靠动作。错误项：20kΩ/7kΩ偏低，绝缘已受损仍可能不动作；60kΩ/30kΩ偏高易误动；80kΩ/40kΩ过高，正常绝缘波动即跳闸，无法运行。"},{"id":93,"type":"single","stem":"井下电气设备隔爆外壳上紧固螺栓缺失一个，现场处理时正确做法是","options":["用规格相同的普通螺栓临时补齐","用铁丝绑扎固定缺口部位","停止使用并按规定补齐专用螺栓","降低该设备负荷后继续运行"],"answer":[2],"explanation":"知识点：隔爆外壳紧固件完整性的失爆判定。正确项：缺少紧固螺栓即构成失爆，必须停用并补齐规定螺栓。错误项：普通螺栓强度、螺距不匹配，不能替代隔爆专用螺栓；铁丝绑扎无法保证隔爆间隙；降负荷运行不能消除失爆隐患。"},{"id":94,"type":"single","stem":"井下电气作业中，操作高压电气设备主回路时，必须执行的组织措施是","options":["工作票制度、工作许可制度、工作监护制度","停送电制度、验电制度、挂牌制度","交接班制度、巡回检查制度、设备包机制度","两票三制中的操作票和监护复诵制度"],"answer":[0],"explanation":"知识点：高压电气设备检修的组织措施。正确项：高压主回路作业须执行工作票、工作许可、工作监护三项组织措施。错误项：停送电、验电、挂牌属于技术措施范畴；交接班、巡检、包机是日常管理制度；操作票和监护复诵是倒闸操作要求，不能替代高压检修组织措施。"},{"id":95,"type":"single","stem":"井下电气设备防爆检查中，隔爆外壳透明件（观察窗）出现裂纹但未脱落，应判定为","options":["可继续使用但需记录观察","失爆，必须停止使用","可用环氧树脂粘补后使用","降低使用电压后可继续使用"],"answer":[1],"explanation":"知识点：隔爆外壳透明件完整性要求。正确项：观察窗有裂纹即失去隔爆性能，判定失爆，必须停用。错误项：记录观察不能消除失爆风险；粘补无法恢复隔爆强度；降低电压不改变外壳隔爆性能失效的事实。"},{"id":96,"type":"single","stem":"井下电缆连接时，采用冷压连接管压接后，接头处绝缘恢复的正确做法是","options":["缠绕绝缘胶带后套热缩管加热收缩","直接缠绕绝缘胶带三层即可","涂绝缘漆后包扎纱布","套普通塑料管用胶带固定"],"answer":[0],"explanation":"知识点：井下电缆接头绝缘恢复工艺。正确项：先缠绕绝缘胶带再套热缩管加热收缩，才能保证绝缘和密封性能。错误项：仅缠胶带无密封，井下潮湿易击穿；绝缘漆加纱布不防水不阻燃；普通塑料管不耐温不密封，均不符合要求。"},{"id":97,"type":"single","stem":"井下移动变电站低压侧馈电开关频繁跳闸，检查发现负荷电流未超整定值，最应优先排查的是","options":["开关过流整定值是否偏小","变压器分接头是否接错","电缆截面是否偏小","电机功率是否偏大"],"answer":[0],"explanation":"知识点：馈电开关频繁跳闸的整定值排查。正确项：负荷电流未超整定值却频繁跳闸，应优先核查过流整定值是否被调小或整定错误。错误项：分接头接错影响电压而非直接跳闸；电缆截面偏小是长期发热问题；电机功率偏大属设计问题，不解释频繁跳闸。"},{"id":98,"type":"single","stem":"井下电气设备安装时，隔爆面之间的间隙若超过规定值，正确的处理方式是","options":["加厚密封垫片缩小间隙","打磨隔爆面使表面更平整","更换合格外壳或按规定修复","涂更多防锈油填充间隙"],"answer":[2],"explanation":"知识点：隔爆间隙超限的处置。正确项：间隙超限必须更换合格外壳或按规定修复，恢复隔爆性能。错误项：加垫片改变隔爆结构；打磨会减小有效接合面长度；涂油不能填充间隙且可能影响隔爆性能。"},{"id":99,"type":"multi","stem":"井下电气设备发生漏电故障后，正确的处置措施包括哪些","options":["立即停止该线路供电并挂牌","查明漏电点并处理合格后送电","用兆欧表测量绝缘电阻确认合格","未查明原因时先合闸试送一次","漏电保护可暂时退出运行以便生产"],"answer":[0,1,2],"explanation":"知识点：漏电故障处置程序。正确项：停止供电挂牌、查明处理、测绝缘合格是标准程序。错误项：未查明原因试送电可能扩大事故；退出漏电保护运行属严重违章，均不可取。"},{"id":100,"type":"single","stem":"井下检漏继电器动作后，在未查明原因前正确的处置方式是","options":["试送电一次观察是否再动作","将该保护短接后继续送电","断开该保护单独给设备送电","待原因查清并处理后送电"],"answer":[3],"explanation":"检漏继电器动作说明电网绝缘可能低于允许值，必须查明并处理故障后才能送电。试送电可能扩大故障；短接保护属于甩保护运行；甩开保护单独送电同样使漏电保护失效，均属严重违章。"},{"id":101,"type":"single","stem":"井下电气设备接线嘴的密封圈内径与电缆外径之间的配合要求是","options":["内径略大于电缆外径便于穿入","内径与电缆外径紧密配合","内径略小于电缆外径靠挤压密封","内径按电缆外径加两毫米选取"],"answer":[1],"explanation":"密封圈内径应与电缆外径紧密配合，才能实现可靠的隔爆密封。内径过大电缆可在圈内窜动漏气；内径过小会割伤电缆护套；加两毫米选取属于人为放大间隙，均破坏隔爆性能。"},{"id":102,"type":"single","stem":"井下运行中的电气设备需要打开隔爆外壳检修时，首先应完成的操作是","options":["用验电笔确认无电后开盖","切断上一级电源并闭锁挂牌","通知调度后直接开盖检查","先松开螺栓释放内部压力"],"answer":[1],"explanation":"打开隔爆外壳前必须先切断上一级电源、闭锁并悬挂停电牌，这是防止误送电的根本措施。仅验电不能防止他人误送电；通知调度不等于停电闭锁；隔爆外壳内部无压力需要释放，该说法混淆了压力容器操作。"},{"id":103,"type":"single","stem":"井下电气设备的局部接地极采用钢管时，其埋设方式正确的是","options":["垂直埋入底板并保持一定深度","水平放置在巷道底板上","倾斜插入帮壁岩层中","垂直插入水沟底部淤泥中"],"answer":[0],"explanation":"局部接地极应垂直埋入底板，保证与潮湿土壤充分接触以降低接地电阻。水平放置接触面积小；插入帮壁岩层无法保证与土壤接触；插入淤泥中因介质不稳定且易腐蚀，均不能保证接地可靠性。"},{"id":104,"type":"single","stem":"井下选用电气设备的防爆形式时，对于正常运行时产生火花或电弧的设备应选用","options":["矿用一般型设备","隔爆型或本质安全型设备","增安型设备单独使用","防水型设备加防护罩"],"answer":[1],"explanation":"正常运行中产生火花或电弧的设备必须采用隔爆型或本质安全型，才能防止引燃瓦斯煤尘。矿用一般型无防爆能力；增安型仅适用于正常时不产生火花电弧的设备；防水型加防护罩不具备隔爆功能。"},{"id":105,"type":"single","stem":"井下电缆与电气设备连接时，电缆护套伸入接线嘴内的长度要求是","options":["护套伸入器壁内五至十五毫米","护套与器壁外端面平齐","护套伸入器壁内一至两毫米","护套完全留在接线嘴外部"],"answer":[0],"explanation":"电缆护套应伸入接线嘴器壁内五至十五毫米，既能被密封圈可靠夹紧又不会割伤芯线。与器壁平齐或只伸入一两毫米时密封圈夹持长度不足；护套完全留在外部则密封圈直接压在芯线上，均不能保证密封和隔爆。"},{"id":106,"type":"single","stem":"井下低压馈电开关中，漏电闭锁与漏电保护的区别在于漏电闭锁的作用是","options":["在电网漏电后延时切除故障","在送电前检测绝缘并闭锁送电","在运行中监测并显示绝缘值","在漏电后自动重合闸一次"],"answer":[1],"explanation":"漏电闭锁是在开关合闸送电前检测电网绝缘，绝缘不合格时闭锁开关使其不能合闸。漏电后延时切除属于漏电保护动作；运行中监测显示是绝缘监测功能；漏电后自动重合闸是馈电开关的另设功能，均与漏电闭锁的定义不符。"},{"id":107,"type":"single","stem":"井下用兆欧表测量电缆绝缘电阻时，正确的操作顺序是","options":["先接好线再匀速摇动手柄","先摇动手柄达到额定转速再接线路","接线后快速摇动读取最大值","接线后断续摇动取平均值"],"answer":[0],"explanation":"测量绝缘电阻应先将兆欧表测试线接好，再匀速摇动手柄至额定转速读数。先摇后接会在接线瞬间对人和设备产生电击；快速摇动读数不稳；断续摇动无法得到稳定读数，均不符合测量要求。"},{"id":108,"type":"single","stem":"井下隔爆开关运行中隔爆外壳温度过高，下列判断中正确的是","options":["外壳温度高说明内部接触电阻过大","外壳温度高说明隔爆面密封不良","外壳温度高说明内部绝缘已击穿","外壳温度高说明保护装置已动作"],"answer":[0],"explanation":"隔爆外壳温度异常升高多因内部触头接触不良、接触电阻增大导致发热。隔爆面密封不良主要影响隔爆性能而非直接引起外壳温升；绝缘击穿通常伴随漏电保护动作；保护动作与外壳温度无直接因果关系。"},{"id":109,"type":"single","stem":"某掘进工作面局部通风机突然停风，班长要求电工立即送电恢复通风，电工的正确做法是","options":["检查瓦斯后按班长要求送电","先送电再检查瓦斯浓度","拒绝送电并撤出人员等待恢复","短接风电闭锁后送电通风"],"answer":[2],"explanation":"停风后必须撤出人员、切断电源，待通风机恢复并检查瓦斯合格后方可送电，严禁在停风状态下送电。先送电或检查瓦斯后送电都可能因瓦斯积聚引发爆炸；短接风电闭锁属于严重违章，会使瓦斯超限时设备仍能运行。"},{"id":110,"type":"single","stem":"井下低压橡套电缆在连接电气设备时，喇叭嘴压紧后电缆护套的伸出长度应控制在什么范围","options":["刚好与喇叭嘴内缘平齐，不露出护套","伸入接线腔5至15毫米，便于压紧","伸出喇叭嘴外5至15毫米，便于观察","护套剥除后直接压紧，无需考虑伸出量"],"answer":[2],"explanation":"知识点：橡套电缆引入装置的密封要求。护套需伸出喇叭嘴外5至15毫米，才能被压紧环有效夹持并形成密封。错误项A会使压紧环直接压在芯线上，失去密封；B伸入腔内无法被压紧环夹持；D剥除护套后压紧环压不到护套，密封失效。"},{"id":111,"type":"single","stem":"井下电气设备隔爆外壳上的紧固螺栓在检修后复装时，正确的做法是","options":["全部螺栓拧紧至弹簧垫圈压平即可","隔爆面螺栓可少装一个，用密封胶填补孔位","用规格相同但长度略长的螺栓替代丢失的螺栓","弹簧垫圈丢失后用普通平垫圈替代"],"answer":[0],"explanation":"知识点：隔爆外壳紧固件要求。螺栓须齐全并拧紧至弹簧垫圈压平，才能保证隔爆面间隙和紧固力。B少装螺栓会降低外壳强度并破坏隔爆性能；C螺栓过长可能顶到内部元件或使隔爆面受力不均；D平垫圈无防松作用，不能替代弹簧垫圈。"},{"id":112,"type":"single","stem":"井下检漏继电器在馈电开关合闸前进行试验时，若按下试验按钮后开关不跳闸，正确的判断是","options":["检漏继电器动作可靠，可以正常送电","试验回路断线或继电器失灵，必须停电处理","电网绝缘电阻过高，属正常现象","需连续按三次试验按钮，若不跳闸再处理"],"answer":[1],"explanation":"知识点：检漏继电器试验要求。试验按钮模拟漏电，正常应立即使馈电开关跳闸；不跳闸说明试验回路断线或继电器失灵，必须停电处理。A与试验目的相反；C电网绝缘高不影响试验回路动作；D多次按压不能替代对失灵回路的排查。"},{"id":113,"type":"single","stem":"井下电气设备防爆检查中，发现隔爆接合面有轻微锈蚀但未超过隔爆参数要求，正确的处理方式是","options":["用砂纸打磨至露出金属光泽并涂防锈油","用棉纱擦净后涂少量凡士林即可","锈蚀不影响隔爆性能，无需处理","用錾子剔除锈层后再用砂纸修整"],"answer":[0],"explanation":"知识点：隔爆面维护。轻微锈蚀须用砂纸打磨至露出金属光泽并涂防锈油，恢复隔爆性能。B棉纱擦净不能除锈，凡士林不能替代打磨；C锈蚀会增大隔爆面间隙，不能忽视；D錾子会损伤隔爆面，破坏隔爆参数。"},{"id":114,"type":"single","stem":"井下移动变电站低压侧漏电保护装置的动作电阻值整定，应依据下列哪项原则确定","options":["按人体安全电流和电网电压计算限定值","按设备额定电流的百分之十整定","按电缆长度每百米增加五欧姆整定","按上一级漏电保护动作值的一半整定"],"answer":[0],"explanation":"知识点：漏电保护整定原则。动作电阻值应保证流过人体的电流不超过安全值，按人体安全电流和电网电压计算限定值。B与额定电流无关；C电缆长度影响绝缘水平但不按此简单叠加整定；D上下级配合需考虑时限，动作值不能简单取半。"},{"id":115,"type":"single","stem":"井下电气作业中，用兆欧表测量电缆绝缘电阻时，正确的接线方式是","options":["兆欧表L端接电缆芯线，E端接电缆铠装或接地芯线","兆欧表L端接电缆铠装，E端接电缆芯线","兆欧表G端接电缆芯线，L端接接地芯线","兆欧表L端和E端都接电缆芯线，G端悬空"],"answer":[0],"explanation":"知识点：兆欧表测量绝缘电阻接线。L端接被测导体即电缆芯线，E端接电缆铠装或接地芯线，读数才反映芯线对地绝缘。B接反会使读数反映铠装对地而非芯线绝缘；C屏蔽端G不应作为测量端接芯线；D两端接同一芯线无法形成对地测量回路。"},{"id":116,"type":"single","stem":"井下电气设备安装时，电缆与设备连接处的密封圈内径与电缆外径的配合要求是","options":["密封圈内径与电缆外径的差值不大于1毫米","密封圈内径应比电缆外径大3至5毫米","密封圈内径应比电缆外径小2毫米以压紧","密封圈内径与电缆外径相等即可，不需考虑公差"],"answer":[0],"explanation":"知识点：电缆引入装置密封圈配合。密封圈内径与电缆外径差值不大于1毫米，才能保证密封圈紧箍电缆形成隔爆密封。B间隙过大会漏气失爆；C内径过小无法套入或割伤电缆；D相等时无过盈量，密封不可靠。"},{"id":117,"type":"single","stem":"井下电气检修中，停电后验电、放电、挂接地线的正确顺序是","options":["验电、放电、挂接地线","放电、验电、挂接地线","挂接地线、验电、放电","验电、挂接地线、放电"],"answer":[0],"explanation":"知识点：检修安全操作程序。必须先验电确认无电，再对地放电消除残余电荷，最后挂接地线防止意外送电。B未验电先放电可能带电放电伤人；C未验电未放电就挂接地线极其危险；D未放电就挂接地线，残余电荷可能通过接地线放电伤人。"},{"id":118,"type":"single","stem":"井下某掘进工作面馈电开关频繁跳闸，复位后可合闸但运行一段时间又跳闸，最应先检查的项目是","options":["开关的过流整定值是否与负荷匹配","隔爆外壳紧固螺栓是否齐全","操作手柄的机械灵活程度","开关外壳的接地是否牢固"],"answer":[0],"explanation":"知识点：馈电开关频繁跳闸的故障判断。能复位合闸说明保护动作而非机械卡死，运行一段时间跳闸多为过流或漏电保护动作，应优先核对过流整定值与实际负荷是否匹配。B螺栓齐全影响隔爆不影响跳闸；C手柄灵活影响操作不影响保护动作；D接地牢固是安全要求，不是频繁跳闸的直接原因。"},{"id":119,"type":"single","stem":"井下电工在检修一台隔爆型磁力启动器时，发现隔爆腔内壁有少量凝结水珠，正确的处置是","options":["用棉纱擦干内壁并检查密封和呼吸装置","直接合盖送电，水珠不影响隔爆性能","用清水冲洗内壁后再擦干","打开盖子晾晒一天后直接送电"],"answer":[0],"explanation":"知识点：隔爆腔内凝结水的处理。水珠会降低绝缘并腐蚀元件，应擦干并检查密封和呼吸装置是否失效，防止再次凝露。B带水送电易造成短路；C清水冲洗会加重受潮；D仅晾晒不检查密封和呼吸装置，凝露会再次发生。"},{"id":120,"type":"single","stem":"煤矿井下检漏继电器对馈电开关实现跳闸控制的接入方式是","options":["检漏继电器常开触点串入开关脱扣线圈回路","检漏继电器常闭触点串入开关脱扣线圈回路","检漏继电器触点并联在开关合闸按钮两端","检漏继电器触点串入开关合闸线圈回路"],"answer":[1],"explanation":"知识点：检漏继电器与馈电开关的配合。漏电时检漏继电器动作，其常闭触点断开使脱扣线圈失电跳闸，故为常闭触点串入脱扣回路。常开触点漏电时闭合反而不跳闸；并联在合闸按钮两端会误合闸；串入合闸回路只影响合闸不影响跳闸。"},{"id":121,"type":"single","stem":"井下用摇表测量电缆绝缘电阻时，测得绝缘电阻为零，最可能的判断是","options":["电缆受潮绝缘下降","电缆芯线之间短路或接地","电缆绝缘老化但未击穿","摇表电池电压不足"],"answer":[1],"explanation":"知识点：绝缘电阻测量结果分析。绝缘电阻为零说明芯线间或芯线对地直接导通，即短路或接地。受潮、老化通常表现为绝缘电阻降低但不为零；摇表电池不足会使指针不稳或读数偏大，不会稳定为零。"},{"id":122,"type":"single","stem":"井下电气设备运行中需要打开隔爆外壳带电检修时，正确的做法是","options":["确认瓦斯浓度低于1%后可以开盖检修","切断上一级电源并验电放电后再开盖检修","由专职瓦斯检查员监护下可以开盖带电检修","停电后立即开盖以防瓦斯积聚"],"answer":[1],"explanation":"知识点：井下电气检修基本安全程序。必须切断上一级电源、验电、放电、挂牌后再开盖，严禁带电打开隔爆外壳。瓦斯浓度合格不是带电开盖的条件；监护不能替代停电；停电后立即开盖未验电放电存在残余电荷和反送电风险。"},{"id":123,"type":"single","stem":"井下电缆悬挂时，电缆与压风管、供水管在巷道同一侧敷设时，电缆应悬挂在管子的","options":["上方并保持0.1米距离","下方并保持0.3米距离","上方并保持0.3米距离","同一水平并保持0.5米距离"],"answer":[2],"explanation":"知识点：井下电缆悬挂间距要求。电缆应敷设在管子上方并保持0.3米以上距离，防止管子漏水或维修时损坏电缆。下方敷设易被滴水浸湿和检修砸伤；0.1米间距过小不符合要求；同一水平敷设易受管路维修影响。"},{"id":124,"type":"single","stem":"井下照明信号综合保护装置中，短路保护与漏电保护同时动作时，优先显示并闭锁的应是","options":["短路故障","漏电故障","过载故障","断相故障"],"answer":[1],"explanation":"知识点：综合保护装置故障判别。漏电保护动作后须闭锁并优先显示漏电，因为漏电可能危及人身安全且可能引发瓦斯爆炸，需先查明绝缘状况。短路虽严重但保护动作后一般可直接判断；过载、断相不会与漏电同时优先闭锁。"},{"id":125,"type":"single","stem":"井下电气设备防爆检查中，发现隔爆外壳紧固螺栓缺少一只，正确的处置是","options":["暂时用规格相近的螺栓代替并记录","用铁丝临时绑扎固定后继续运行","立即停止运行并按规定补齐同规格螺栓","在缺少螺栓处涂密封胶后继续运行"],"answer":[2],"explanation":"知识点：隔爆外壳完整性的要求。隔爆外壳紧固螺栓缺失会破坏隔爆性能，必须停止运行并补齐同规格螺栓。用相近螺栓、铁丝绑扎、涂密封胶均不能保证隔爆间隙和强度，属违规处置。"},{"id":126,"type":"single","stem":"井下低压馈电开关中，JDB型电动机综合保护器的主要保护功能是","options":["过载、短路、断相、漏电闭锁","过载、短路、断相、过压","过载、短路、漏电、欠压","短路、断相、漏电、超温"],"answer":[0],"explanation":"知识点：JDB综合保护器功能。JDB型电动机综合保护器具有过载、短路、断相和漏电闭锁保护功能。过压、欠压、超温不是其标准保护项目，容易与其它保护装置功能混淆。"},{"id":127,"type":"single","stem":"井下电气作业中，验电时应使用与电源电压等级相适应的验电笔，验电顺序应是","options":["先验中性线后验相线","先验相线后验中性线","先验负荷侧后验电源侧","先验电源侧后验负荷侧"],"answer":[1],"explanation":"知识点：验电操作程序。验电应先验相线后验中性线，相线带电是主要危险源，先确认相线无电再验中性线。先验中性线可能因中性线断开而误判；负荷侧与电源侧顺序不是验电的核心要求。"},{"id":128,"type":"single","stem":"井下移动变电站低压侧漏电保护动作后，经检查发现是电缆受潮，正确的恢复送电程序是","options":["烘干电缆后直接合闸试送电","摇测绝缘电阻合格后按程序恢复送电","将漏电保护退出后试送电观察","更换漏电保护插件后直接送电"],"answer":[1],"explanation":"知识点：漏电故障处理后的送电程序。电缆受潮处理后必须摇测绝缘电阻合格，确认绝缘恢复后方可按程序送电。直接合闸、退出保护、更换插件均未确认绝缘状况，可能再次漏电或扩大事故。"},{"id":129,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面涂防锈油时，正确的做法是","options":["涂凡士林后擦去多余油脂形成薄层","涂钙基润滑脂后立即装配","涂机油后静置十分钟再装配","涂防锈漆保证长期不锈"],"answer":[0],"explanation":"知识点：隔爆结合面需保持清洁并涂薄层防锈油脂，常用凡士林且不得积存过多油脂，以免影响隔爆间隙。选项0正确；选项1钙基脂黏稠易积存，影响结合面间隙；选项2机油易流失且静置会吸附煤尘；选项3防锈漆会增大结合面间隙、破坏隔爆性能。"},{"id":130,"type":"single","stem":"井下检漏保护装置对网路绝缘电阻的监测，其动作电阻值整定的依据是","options":["电网额定电压等级","变压器容量大小","电缆截面粗细","负荷电流大小"],"answer":[0],"explanation":"知识点：漏电保护动作电阻值按电网额定电压等级整定，不同电压等级对应不同动作值。选项0正确；选项1容量只影响短路保护整定；选项2截面影响载流量；选项3负荷电流与漏电动作值无关。"},{"id":131,"type":"single","stem":"井下电气设备运行中需要打开隔爆外壳检查时，正确的操作顺序是","options":["先停电、验电、放电，再打开外壳","先打开外壳观察，再决定是否停电","先通知调度，再带电打开外壳","先断开负荷开关，随即打开外壳"],"answer":[0],"explanation":"知识点：检修隔爆设备必须先停电、验电、放电并挂牌，确认无电后方可开盖。选项0正确；选项1带电开盖属严重违章；选项2通知调度不能代替停电验电；选项3断开负荷开关后未验电放电，可能仍带电或存有残余电荷。"},{"id":132,"type":"single","stem":"井下电缆与电气设备连接时，对电缆芯线连接的要求是","options":["采用压接或焊接，连接牢固并保持绝缘","铜芯与铝芯可直接绞接后包绝缘","多股芯线可切除部分股线后插入接线嘴","芯线连接后可用黑胶布缠绕代替绝缘套管"],"answer":[0],"explanation":"知识点：电缆芯线必须采用压接或焊接等可靠方式连接，并恢复绝缘。选项0正确；选项1铜铝直接连接会产生电化学腐蚀；选项2切除股线会减小载流截面；选项3黑胶布不能代替规定的绝缘套管和接线工艺。"},{"id":133,"type":"single","stem":"井下局部通风机供电采用的“三专”是指","options":["专用变压器、专用开关、专用线路","专用电缆、专用开关、专用保护","专用电源、专用变压器、专用电缆","专用开关、专用线路、专用接地"],"answer":[0],"explanation":"知识点：局部通风机“三专”为专用变压器、专用开关、专用线路，保证局部通风机可靠供电。选项0正确；选项1、2、3均把“三专”内容与其他供电要求混淆，缺少专用变压器这一核心项。"},{"id":134,"type":"single","stem":"井下运行中的电气设备需要停送电时，执行“谁停电、谁送电”制度的主要目的是","options":["防止误送电造成检修人员触电","减少停电对生产的影响","明确停送电操作的时间记录","便于调度室掌握设备运行状态"],"answer":[0],"explanation":"知识点：停送电由同一人负责可防止他人误送电，保障检修人员安全。选项0正确；选项1、3是次要作用；选项2时间记录不是该制度的核心目的。"},{"id":135,"type":"single","stem":"隔爆型电气设备外壳上标志“ExdI”中的“I”表示该设备适用于","options":["煤矿井下有甲烷气体的环境","工厂有氢气气体的环境","有腐蚀性气体的场所","有粉尘爆炸危险的场所"],"answer":[0],"explanation":"知识点：ExdI中I类表示煤矿井下用电气设备，适用甲烷环境。选项0正确；选项1氢气属II类工厂用；选项2腐蚀性气体不是防爆类别含义；选项3粉尘防爆另有标志。"},{"id":136,"type":"single","stem":"井下电气设备保护接地网中，接地极与接地导线连接处的要求是","options":["连接牢固并有防松措施，接触良好","用铁丝缠绕后埋入接地坑","焊接后涂漆防腐即可","用螺栓压紧但不必防松"],"answer":[0],"explanation":"知识点：接地连接必须牢固可靠、接触良好并有防松措施，保证接地电阻合格。选项0正确；选项1铁丝缠绕接触不可靠；选项2涂漆会增大接触电阻；选项3无防松措施易因振动松脱。"},{"id":137,"type":"single","stem":"井下移动变电站低压侧发生漏电故障，检漏继电器动作后，电工的正确处置是","options":["查明并排除漏电故障，绝缘合格后再送电","将检漏继电器退出运行后送电","加大漏电动作电阻整定值后送电","断开漏电支路的接地线后送电"],"answer":[0],"explanation":"知识点：漏电保护动作后必须查明原因、排除故障、绝缘合格才可恢复送电。选项0正确；选项1退出保护属严重违章；选项2随意放大整定值会失去保护作用；选项3断开接地线破坏保护接地系统。"},{"id":138,"type":"single","stem":"井下电气设备的防爆标志“ExdI”中，字母“d”表示该设备属于哪种防爆型式","options":["增安型","隔爆型","本质安全型","正压型"],"answer":[1],"explanation":"知识点：防爆标志字母含义。d 表示隔爆型，靠外壳承受内部爆炸而不传爆，故正确。增安型标志为 e；本质安全型标志为 i；正压型标志为 p，三者均与 d 不符。"},{"id":139,"type":"single","stem":"井下电缆同橡套电缆的接地芯线，除用作监测接地回路外，还可以兼作","options":["控制芯线使用","信号芯线使用","其他用途使用","以上均不可以"],"answer":[3],"explanation":"知识点：接地芯线的用途限制。接地芯线专用于接地和监测回路，不得兼作其他用途，故正确。兼作控制芯线会因接地故障导致误动作；兼作信号芯线会引入干扰并使接地监测失效；兼作其他用途同样破坏接地保护的独立性。"},{"id":140,"type":"single","stem":"井下电气设备运行中，若发现隔爆外壳的隔爆接合面出现轻微锈蚀但未超过规定间隙，正确的处置是","options":["立即更换整个外壳","除锈涂油后继续使用","用砂纸打磨并加大间隙","用油漆覆盖锈蚀部位"],"answer":[1],"explanation":"知识点：隔爆接合面锈蚀的处理。轻微锈蚀未超间隙时，除锈并涂凡士林可恢复防锈性能，故正确。立即更换外壳属过度处置；打磨会改变接合面间隙破坏隔爆性能；油漆覆盖不能除锈且油漆层会影响间隙。"},{"id":141,"type":"single","stem":"井下电气设备检修中，需要打开隔爆外壳时，正确的操作顺序是","options":["先断上级电源并验电放电后打开","先打开外壳再断开电源","先断开负荷侧开关再打开","先挂接地线再停上级电源"],"answer":[0],"explanation":"知识点：打开隔爆外壳的停电程序。必须先停上级电源、验电、放电，确认无电后才准打开，故正确。先开壳再断电属带电作业；只断负荷侧开关上级电源仍可能反送电；先挂接地线再停电源顺序颠倒，未停电挂接地线无意义且危险。"},{"id":142,"type":"single","stem":"井下低压电网中，用于防止人身触电和漏电事故的主要保护装置是","options":["过流保护装置","漏电保护装置","失压保护装置","断相保护装置"],"answer":[1],"explanation":"知识点：漏电保护的功能。漏电保护装置检测电网对地绝缘并动作，防止触电和漏电事故，故正确。过流保护防短路和过载；失压保护防电压消失后自启动；断相保护防电动机缺相运行，均不针对漏电触电。"},{"id":143,"type":"single","stem":"井下电气设备搬迁后重新安装，在送电前必须完成的工作是","options":["测量设备绝缘电阻并做接地检查","先送电试运行再检查接地","先送电观察指示灯再紧固接线","先拆除漏电保护再送电调试"],"answer":[0],"explanation":"知识点：设备搬迁后送电前的检查。搬迁可能损伤绝缘和接地，送电前必须测绝缘并检查接地，故正确。先送电试运行可能因绝缘损坏造成短路；先送电观察指示灯同样冒险；拆除漏电保护送电则使保护失效。"},{"id":144,"type":"single","stem":"井下使用普通型电气仪表测量带电回路时，可能引起的最严重后果是","options":["仪表读数不准","产生电火花引爆瓦斯","仪表外壳发热","测量线缆过长"],"answer":[1],"explanation":"知识点：井下仪表使用的防爆要求。普通型仪表在带电测量时可能产生电火花，遇瓦斯煤尘可引爆，故正确。读数不准、外壳发热、线缆过长均非最严重后果，且在井下环境中电火花引爆才是核心风险。"},{"id":145,"type":"single","stem":"井下电气设备运行中突然闻到焦糊味并发现接线腔温度明显升高，此时正确的第一步处置是","options":["立即断开该设备电源并汇报","先打开接线腔查看发热点","先降低负荷继续观察运行","先测量电流判断是否过载"],"answer":[0],"explanation":"知识点：电气设备异常发热的应急处置。焦糊味和温度升高预示绝缘过热或短路，应立即断电并汇报，故正确。带电打开接线腔可能触电或引发爆炸；降负荷继续运行可能扩大故障；先测电流需带电操作且延误断电时机。"},{"id":146,"type":"single","stem":"井下某采区变电所检漏继电器频繁动作，经查为电缆受潮绝缘下降，正确的处理环节是","options":["更换受潮电缆并复查绝缘","调高漏电动作整定值","将检漏继电器暂时停用","在电缆上并联电阻降低灵敏度"],"answer":[0],"explanation":"知识点：漏电频繁动作的故障处理。绝缘下降应更换或干燥处理电缆并复查绝缘，故正确。调高整定值会降低保护灵敏度；停用检漏继电器使漏电保护失效；并联电阻会改变检测回路参数，使保护误判或失效。"},{"id":147,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因之前正确的处置是","options":["先试送电一次观察是否再跳闸","将检漏保护退出后继续送电","查明并消除漏电原因后再送电","把漏电闭锁值调大后送电"],"answer":[2],"explanation":"知识点：漏电保护动作后的处置。必须查明原因、消除故障后才能恢复送电。试送电可能扩大事故；退出保护属严重违章；调大闭锁值会失去保护作用，均错误。"},{"id":148,"type":"single","stem":"井下电气设备接线嘴与电缆之间使用密封圈时，密封圈内径与电缆外径的配合要求是","options":["内径略大于电缆外径以便穿入","内径等于电缆外径并紧密配合","内径略小于电缆外径以压紧电缆","内径按接线嘴内径选配即可"],"answer":[1],"explanation":"知识点：电缆引入装置的密封。密封圈内径应与电缆外径紧密配合，保证隔爆性能。略大则间隙超标失爆；略小会损伤电缆且难装配；按接线嘴内径选配忽略了电缆尺寸，均错误。"},{"id":149,"type":"single","stem":"井下低压馈电开关中，过流保护整定值应按什么原则确定","options":["按被保护线路最大负荷电流并躲过电机启动电流","按被保护线路额定电流的十分之一整定","按上级开关整定值的一半整定","按电缆长期允许载流量的两倍整定"],"answer":[0],"explanation":"知识点：过流保护整定原则。应按最大负荷电流并躲过启动电流，保证正常启动不误动、故障时可靠动作。按额定电流十分之一会频繁误动；按上级一半无依据且可能失去选择性；按载流量两倍与保护配合无关。"},{"id":150,"type":"single","stem":"井下电气设备运行中，隔爆外壳出现下列哪种情况即判定为失爆","options":["外壳表面有轻微油漆脱落","隔爆接合面有锈蚀但间隙合格","外壳上有未贯穿的凹陷变形","隔爆接合面紧固螺栓缺少弹簧垫圈"],"answer":[3],"explanation":"知识点：失爆判定。紧固螺栓缺少弹簧垫圈属于失爆，因为螺栓可能松动导致间隙超标。油漆脱落不影响隔爆；接合面锈蚀但间隙合格需处理但非必然失爆；未贯穿凹陷未影响隔爆结构，均不属于失爆。"},{"id":151,"type":"single","stem":"井下电气作业中，验电环节的正确操作顺序是","options":["先验低压后验高压，先验近处后验远处","先验高压后验低压，先验近处后验远处","先验低压后验高压，先验远处后验近处","先验高压后验低压，先验远处后验近处"],"answer":[0],"explanation":"知识点：验电顺序。应先验低压后验高压、先验近处后验远处，逐步确认无电。先高压后低压顺序颠倒；先远处后近处不符合由近及远确认原则，均错误。"},{"id":152,"type":"single","stem":"井下移动变电站高压侧电缆连接器在运行中发热严重，最可能的原因是","options":["连接器插接不到位导致接触电阻增大","电缆截面偏大导致电流密度过低","环境温度偏低导致散热过快","绝缘电阻偏高导致泄漏电流偏小"],"answer":[0],"explanation":"知识点：电缆连接器发热原因。插接不到位使接触电阻增大，运行中发热。截面偏大、温度偏低、绝缘偏高都不会造成发热，属干扰项。"},{"id":153,"type":"single","stem":"井下电气设备检修时，验电后确认无电，下一步应做的工作是","options":["立即用手触摸导体确认是否带电","对可能送电到检修设备的开关挂牌并装设接地线","直接开始拆卸设备外壳进行检修","测量设备绝缘电阻判断能否检修"],"answer":[1],"explanation":"知识点：停电检修安全措施。验电确认无电后应挂牌并装设接地线，防止误送电和感应电。用手触摸导体危险；直接拆卸缺少接地措施；测绝缘是检修内容而非安全措施，均错误。"},{"id":154,"type":"single","stem":"井下电气设备隔爆接合面的间隙超过规定值时，正确的处理方式是","options":["用油漆填补间隙后继续使用","更换合格部件或修复至规定间隙","加装橡胶垫片调整间隙","在接合面涂满润滑脂填充间隙"],"answer":[1],"explanation":"知识点：隔爆间隙超标处理。必须更换或修复至规定间隙。油漆、橡胶垫片、润滑脂都不能替代金属隔爆面，填充后仍属失爆，均错误。"},{"id":155,"type":"single","stem":"井下电气设备发生漏电故障后，检漏继电器动作，此时在故障未查明前对该供电回路正确的做法是","options":["将该回路检漏继电器短接后送电","把该回路负荷转移到另一回路继续生产","保持该回路停电并组织排查故障点","将检漏继电器整定值调高后试送电"],"answer":[2],"explanation":"知识点：漏电故障处置。应保持停电并排查故障。短接继电器、转移负荷、调高整定值都是绕过保护继续送电，属严重违章，均错误。"},{"id":156,"type":"single","stem":"井下检漏保护装置动作后，在恢复送电前必须完成的步骤是","options":["先按下试验按钮验证检漏装置动作正常","先拉开隔离开关再逐台查找故障支路","先合上总开关再观察检漏装置是否再次动作","先断开检漏装置电源再逐台恢复支路"],"answer":[1],"explanation":"知识点：漏电闭锁后恢复送电程序。必须先隔离电源再逐台排查故障支路，确认绝缘合格后才可送电。按试验按钮验证动作正确不能代替查故障；先合总开关观察会再次引发漏电跳闸甚至扩大事故；先断开检漏装置电源再恢复支路属于甩保护运行，严重违规。"},{"id":157,"type":"single","stem":"井下电气设备接线嘴压紧螺母式引入装置中，密封圈内径与电缆外径的配合要求是","options":["密封圈内径应略大于电缆外径便于穿入","密封圈内径应与电缆外径相符并紧密配合","密封圈内径应小于电缆外径靠弹性箍紧","密封圈内径可比电缆外径大两毫米以内"],"answer":[1],"explanation":"知识点：隔爆引入装置密封圈配合要求。密封圈内径应与电缆外径相符、紧密配合，才能保证隔爆和密封性能。内径略大便于穿入会导致间隙超限失爆；内径小于电缆外径会割伤电缆绝缘；允许大两毫米以内同样造成间隙超限，均不符合要求。"},{"id":158,"type":"single","stem":"井下电气作业中，用摇表测量电缆绝缘电阻后，正确的放电顺序是","options":["先断开摇表接线再对电缆芯线放电","先对电缆芯线放电再拆摇表接线","先拆接地端再断开摇表接线并放电","先拆摇表电源再对电缆芯线放电"],"answer":[1],"explanation":"知识点：绝缘电阻测量后的放电操作。测量后电缆芯线存有残余电荷，必须先对芯线放电再拆接线，防止残余电荷伤人。先拆线再放电顺序错误，拆线瞬间可能触电；先拆接地端再拆线同样危险；摇表本身无电源可拆，说法不成立。"},{"id":159,"type":"single","stem":"井下低压馈电开关的过流保护整定值，应根据什么来确定","options":["被保护线路最大负荷电流和短路电流","开关额定电流和电缆截面两者中的较大值","上一级开关整定值和线路长度之差","变压器容量和开关额定电流之比"],"answer":[0],"explanation":"知识点：过流保护整定原则。整定值应按被保护线路最大负荷电流并躲过短路电流来整定，保证选择性。按开关额定电流和电缆截面取大值不符合整定依据；按上级整定值与长度差值计算无此方法；按容量与额定电流之比计算同样不是整定原则。"},{"id":160,"type":"single","stem":"井下电气设备防爆检查中，发现隔爆外壳紧固螺栓缺少弹簧垫圈，正确判定是","options":["属于失爆，必须停电处理后方可运行","可以临时运行但需当班补装弹簧垫圈","只要螺栓拧紧就不影响隔爆性能","在螺栓上缠绕生料带后即可继续运行"],"answer":[0],"explanation":"知识点：隔爆外壳紧固件完整性。缺少弹簧垫圈不能保证螺栓防松，属于失爆，必须停电处理。临时运行并当班补装违反失爆设备不得运行的规定；只拧紧不能替代防松措施；缠绕生料带不是防松措施且可能影响导电，均错误。"},{"id":161,"type":"single","stem":"井下电气设备检修时，验电环节的正确操作是","options":["用电压等级相符的验电器在检修设备各相分别验电","用验电器在检修设备外壳上验电确认无电","用万用表代替验电器测量各相电压判断有无电","用手背轻触导电部位判断是否带电"],"answer":[0],"explanation":"知识点：检修验电操作。必须使用电压等级相符的验电器对各相分别验电。在外壳验电不能判断芯线是否带电；万用表不能替代专用验电器且量程可能不符；用手背轻触判断带电属于严重违章，可能触电。"},{"id":162,"type":"single","stem":"井下移动变电站低压侧漏电保护的动作电阻值整定，主要依据是","options":["人体安全电流和电网对地绝缘水平","变压器容量和低压侧额定电压","上级开关的漏电动作时间和电缆长度","低压侧最大负荷电流和功率因数"],"answer":[0],"explanation":"知识点：漏电保护整定依据。漏电保护动作电阻值应保证人身触电电流不超过安全值，并与电网对地绝缘水平相适应。按变压器容量和额定电压整定不是漏电保护依据；按上级动作时间和电缆长度不是整定电阻值的依据；按最大负荷电流和功率因数是过流保护考虑因素。"},{"id":163,"type":"single","stem":"井下电气设备隔爆接合面的间隙是指","options":["两个接合面之间的最大允许间隙值","隔爆外壳与电缆之间的密封间隙","隔爆腔内零件与外壳之间的活动间隙","接线端子与外壳之间的爬电距离"],"answer":[0],"explanation":"知识点：隔爆接合面间隙定义。隔爆接合面间隙指两个接合面之间允许的最大间隙，超过则失爆。外壳与电缆之间是密封圈密封问题；腔内零件与外壳之间是电气间隙概念；端子与外壳之间是爬电距离概念，均不是隔爆接合面间隙。"},{"id":164,"type":"single","stem":"井下电气设备运行中，隔爆外壳表面温度超过规定限值时，正确的处置是","options":["立即停电检查发热原因并处理","加强通风冷却后继续运行观察","降低负荷运行至检修班再处理","在表面加装散热片后继续运行"],"answer":[0],"explanation":"知识点：隔爆设备温度管理。外壳表面温度超限可能引燃瓦斯煤尘，必须立即停电检查处理。加强通风继续运行不能消除内部发热根源；降负荷运行至检修班仍存在超温引燃风险；加装散热片不能解决内部故障发热问题，均错误。"},{"id":165,"type":"single","stem":"井下电气作业中，停送电操作时正确执行的原则是","options":["谁停电谁送电，并挂停电牌上锁","谁停电谁送电，但可口头委托他人送电","值班长可代替停电人送电并摘牌","检修负责人可代替停电人送电并摘牌"],"answer":[0],"explanation":"知识点：停送电制度。必须坚持谁停电谁送电，并悬挂停电牌、上锁，防止误送电。口头委托他人送电违反制度；值班长代替送电摘牌混淆责任主体；检修负责人代替送电摘牌同样违反谁停电谁送电原则。"},{"id":166,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并处理前，正确的做法是","options":["试送电一次观察是否再次动作","将检漏保护退出运行后送电","查明并处理后才能恢复送电","降低检漏整定值后送电"],"answer":[2],"explanation":"知识点：检漏保护动作后处置。正确项：检漏动作说明存在漏电隐患，必须查明原因并处理后方可恢复送电。错误项：试送电可能造成事故扩大；退出检漏运行属严重违章；降低整定值是掩盖隐患的做法。"},{"id":167,"type":"single","stem":"井下使用中的防爆电气设备，其隔爆外壳上的紧固螺栓缺失一枚时，正确的处置是","options":["用同规格螺栓补齐后继续使用","暂时用铁丝绑扎固定","停止使用并更换或补齐合格螺栓","减少该处密封圈厚度补偿"],"answer":[2],"explanation":"知识点：隔爆外壳完整性要求。正确项：隔爆外壳紧固螺栓缺失会破坏隔爆性能，必须停止使用并补齐合格螺栓后方可运行。错误项：同规格但强度等级不符仍不满足要求，且随意更换可能影响隔爆间隙；铁丝绑扎完全不具隔爆能力；减少密封圈厚度属于破坏性错误做法。"},{"id":168,"type":"single","stem":"井下电气作业中，发现电气设备着火时，首先应进行的操作是","options":["用井下消防水管直接灭火","切断该设备电源","用干粉灭火器灭火","用砂子覆盖灭火"],"answer":[1],"explanation":"知识点：电气火灾处置程序。正确项：电气设备着火首先应切断电源，防止触电和事故扩大，然后再灭火。错误项：未断电用水灭火有触电危险；未断电用干粉灭火器虽不导电但火源未消除；用砂子覆盖同样应在断电后进行。"},{"id":169,"type":"single","stem":"井下电气设备运行中，电动机突然出现声音异常且电流表指示增大，正确的第一步处置是","options":["立即断电停机检查","继续运行观察变化","降低负荷继续运行","加强通风降温后运行"],"answer":[0],"explanation":"知识点：电动机异常运行判断。正确项：声音异常且电流增大说明可能存在机械卡阻或绕组故障，应立即断电停机检查，防止故障扩大。错误项：继续运行观察可能烧毁电机；降低负荷不能消除故障原因；加强通风不能解决电流增大问题。"},{"id":170,"type":"single","stem":"井下变电所值班人员在巡检时发现一台开关外壳温度明显高于同类设备，但运行电流正常，下一步应优先采取的措施是","options":["记录温度继续观察","停电检查内部接头和触头","打开外壳通风降温","降低该回路负荷运行"],"answer":[1],"explanation":"知识点：电气设备过热异常判断。正确项：电流正常而外壳温度异常升高，多因内部接头松动或触头接触不良，应停电检查处理。错误项：仅记录观察会延误处理；带电打开外壳违反规程且危险；降低负荷不能解决接触不良的根本问题。"},{"id":171,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面粗糙度应达到的加工要求是什么","options":["Ra不大于6.3微米","Ra不大于3.2微米","Ra不大于12.5微米","Ra不大于1.6微米"],"answer":[0],"explanation":"知识点：隔爆结合面粗糙度要求。隔爆面需保证爆炸火焰冷却与泄压，粗糙度Ra不大于6.3微米为合格；Ra3.2微米是更精加工要求但并非该处标准；Ra12.5微米过粗会增大间隙泄漏；Ra1.6微米属镜面级加工，成本高且非隔爆面必需。"},{"id":172,"type":"single","stem":"井下检漏保护装置动作后，若需恢复送电，正确的操作顺序是什么","options":["先查明并排除漏电原因，再复位送电","先按下复位按钮试送一次，观察是否再次动作","先将开关打到合闸位置，再检查漏电原因","先甩掉检漏保护，送电后再处理漏电"],"answer":[0],"explanation":"知识点：漏电闭锁与检漏保护动作后的处置程序。检漏动作说明线路存在绝缘隐患，必须先查因排除再送电；先复位试送可能扩大故障；先合闸再查属于带故障强行送电；甩掉保护送电属严重违章，会失去漏电保护。"},{"id":173,"type":"single","stem":"矿用隔爆型电气设备接线时，电缆引入装置的密封圈内径与电缆外径的配合要求是什么","options":["密封圈内径与电缆外径差不大于1毫米","密封圈内径应比电缆外径小2毫米以上","密封圈内径应比电缆外径大3毫米以便穿线","密封圈内径与电缆外径差不大于5毫米"],"answer":[0],"explanation":"知识点：电缆引入装置密封圈配合要求。密封圈内径与电缆外径差不超过1毫米才能保证压紧后有效密封；小2毫米以上会套不进或割伤电缆；大3毫米会形成间隙失爆；大5毫米间隙过大无法密封。"},{"id":174,"type":"single","stem":"井下电气设备的保护接地网中，接地母线与接地极的连接方式应满足什么要求","options":["采用焊接或螺栓压接并保证电气连通可靠","采用铁丝缠绕后埋入地下即可","采用搭接后用绝缘胶带包扎固定","采用锡焊连接后涂防锈漆即可"],"answer":[0],"explanation":"知识点：保护接地连接要求。接地连接必须保证低电阻、机械牢固、耐腐蚀，焊接或螺栓压接合格；铁丝缠绕接触电阻大且易锈断；绝缘胶带包扎会隔断电气通路；锡焊在井下潮湿震动环境易开裂且截面不足。"},{"id":175,"type":"single","stem":"井下低压馈电开关中，过流保护装置的动作电流整定值应根据什么来确定","options":["被保护线路的最大负荷电流和允许过载能力","开关额定电流的1.5倍固定值","电缆截面允许载流量的2倍","变压器高压侧额定电流的折算值"],"answer":[0],"explanation":"知识点：过流保护整定原则。整定值需躲过正常最大负荷电流，同时在线路过载或短路时可靠动作；按开关额定电流固定倍数未考虑实际负荷；按电缆载流量2倍不能反映真实过载；按高压侧折算值不适用于低压馈电保护。"},{"id":176,"type":"single","stem":"井下电缆在巷道内悬挂时，电缆与压风管、供水管平行敷设的间距要求是什么","options":["电缆应敷设在管子上方并保持0.3米以上距离","电缆可与管子紧贴敷设以便固定","电缆应敷设在管子下方并保持0.1米距离","电缆与管子平行敷设时无需规定间距"],"answer":[0],"explanation":"知识点：井下电缆敷设间距要求。电缆应在管路上方并保持0.3米以上，防止管路漏水或检修伤及电缆；紧贴敷设易受潮受损；敷设在下方易被漏水浸泡；无间距规定不符合规程。"},{"id":177,"type":"single","stem":"井下电气作业中，使用摇表测量电缆绝缘电阻时，正确的操作是什么","options":["停电并验电放电后，分别测量相间及相对地绝缘","带电测量相间绝缘以获取真实数据","只测量相对地绝缘，相间绝缘可省略","测量前无需放电，直接接线摇测"],"answer":[0],"explanation":"知识点：绝缘电阻测量操作。必须停电验电放电后测量，且相间和相对地都要测；带电测量摇表会损坏且危险；只测相对地会漏检相间缺陷；不放电可能残余电荷伤人并影响读数。"},{"id":178,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并处理前，作业人员应采取的措施是","options":["将检漏保护短接后继续送电","试送电一次观察是否再次动作","待检漏保护装置恢复后直接恢复送电","查明并消除漏电原因后再恢复送电"],"answer":[3],"explanation":"知识点：漏电闭锁与检漏保护处置。检漏动作说明存在漏电，必须查清并消除原因后才能送电；短接会使保护失效，试送电和直接恢复都可能造成触电或引爆。"},{"id":179,"type":"single","stem":"井下电气设备接线嘴与电缆之间必须使用密封圈，密封圈的硬度应达到的要求是","options":["邵氏硬度45～55","邵氏硬度25～35","邵氏硬度60～70","邵氏硬度75～85"],"answer":[0],"explanation":"知识点：隔爆密封圈硬度要求。密封圈硬度邵氏45～55才能保证压紧后有效密封且不损伤电缆；过硬压不实，过软易变形失去密封。"},{"id":180,"type":"single","stem":"井下电缆悬挂时，两悬挂点之间的距离不得超过的规定值是","options":["1m","3m","5m","10m"],"answer":[1],"explanation":"知识点：井下电缆悬挂间距。电缆悬挂点间距不得超过3m，防止电缆因自重下垂受力而损伤；1m过密不必要，5m和10m间距过大易造成电缆受力磨损。"},{"id":181,"type":"single","stem":"使用中的隔爆型电气设备隔爆外壳出现裂纹但未穿透，正确的处置方式是","options":["用环氧树脂粘补后继续使用","用焊接方法补焊后继续使用","停止使用并更换外壳或升井检修","在裂纹处加装钢板压紧后继续使用"],"answer":[2],"explanation":"知识点：隔爆外壳完整性要求。隔爆外壳有裂纹即失去隔爆性能，必须停用更换或升井检修；粘补、补焊和加装压板都不能恢复隔爆性能。"},{"id":182,"type":"single","stem":"井下电气设备进行停送电操作时，验电环节应使用与电源电压等级相适应的验电器，验电前应先","options":["在有电的设备上试验验电器是否良好","直接在被验设备上验电","用万用表代替验电器验电","用绝缘手套触碰接线端子判断"],"answer":[0],"explanation":"知识点：验电操作程序。验电前必须在有电设备上验证验电器完好，防止验电器失效造成误判；直接验电、用万用表代替或用触碰判断都不能确保安全。"},{"id":183,"type":"single","stem":"井下低压馈电线上装设的漏电闭锁装置，其闭锁动作后对馈电开关的控制方式是","options":["允许合闸但发出声光报警","闭锁馈电开关使其不能合闸","延时10s后自动合闸","仅闭锁漏电支路不影响总开关"],"answer":[1],"explanation":"知识点：漏电闭锁功能。漏电闭锁是在送电前检测到漏电即闭锁开关使其不能合闸；报警不闭锁、延时合闸和仅闭锁支路都不符合漏电闭锁的定义。"},{"id":184,"type":"single","stem":"井下电气设备隔爆接合面的表面粗糙度要求，对隔爆面加工面的粗糙度Ra值应不大于","options":["3.2μm","6.3μm","12.5μm","25μm"],"answer":[1],"explanation":"知识点：隔爆接合面粗糙度。隔爆面Ra不大于6.3μm才能保证接合面贴合紧密、隔爆间隙有效；3.2μm过严非通用要求，12.5μm和25μm过粗会增大间隙影响隔爆。"},{"id":185,"type":"single","stem":"井下移动式电气设备与接地网连接时，应采用的方式是","options":["利用设备外壳与轨道接触接地","用电缆的接地芯线连接接地网","就近打入一根钢管作局部接地","用铁丝临时绑扎在接地扁钢上"],"answer":[1],"explanation":"知识点：移动设备接地连接。移动设备必须通过电缆接地芯线与接地网可靠连接；靠外壳接触轨道、打钢管作局部接地、铁丝绑扎都不能保证接地连续性。"},{"id":186,"type":"single","stem":"某矿掘进工作面局部通风机供电线路发生漏电，检漏继电器动作切断电源，班长要求电工将检漏继电器短接后先恢复通风，电工的正确做法是","options":["按班长要求短接检漏继电器恢复送电","先查明漏电原因并处理后恢复送电","改接另一路电源绕开检漏继电器送电","将检漏继电器整定值调大后送电"],"answer":[1],"explanation":"知识点：漏电处置与违章指挥拒绝。检漏动作必须查清漏电原因处理后送电；短接、绕开、调大整定值都是使保护失效的违章做法，且不能因通风需要而放弃漏电保护。"},{"id":187,"type":"single","stem":"井下检漏保护装置在电网绝缘电阻低于规定值时，其正确动作是","options":["发出声光报警但继续供电","自动切断被保护线路电源","仅记录故障不切断电源","延时十分钟后切断电源"],"answer":[1],"explanation":"知识点：检漏保护装置的核心功能是绝缘监视与漏电闭锁。绝缘电阻低于整定值时，装置应迅速切断被保护线路电源，防止漏电火花引爆瓦斯。错误项：仅报警不切断无法消除引爆风险；只记录不切断同样不消除危险；延时十分钟会在此期间持续存在漏电隐患。"},{"id":188,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面粗糙度要求，正确的做法是","options":["允许有少量锈蚀以增大摩擦","保持清洁并涂适量防锈油脂","隔爆面应涂厚层油漆防腐","允许存在深度不超过1mm的划痕"],"answer":[1],"explanation":"知识点：隔爆结合面的完好性直接决定隔爆性能。结合面须清洁、无锈蚀、无损伤，可涂适量防锈油脂防止锈蚀。错误项：锈蚀会增大间隙破坏隔爆性能；涂厚漆会改变结合面间隙；划痕超限会形成火焰通路，均不允许。"},{"id":189,"type":"single","stem":"井下电气设备的接地电阻值，其接地网上任一保护接地点的接地电阻不得超过","options":["1Ω","2Ω","4Ω","10Ω"],"answer":[1],"explanation":"知识点：煤矿井下保护接地网要求任一保护接地点的接地电阻不超过2Ω，以确保漏电电流可靠入地、降低接触电压。错误项：1Ω要求过严并非规程值；4Ω和10Ω均偏大，无法保证接地保护可靠性。"},{"id":190,"type":"single","stem":"井下电气设备检修后送电前，必须进行的检查项目是","options":["测量设备外壳温度","检查防爆性能并测试绝缘","清点工具数量是否齐全","确认设备外观油漆完好"],"answer":[1],"explanation":"知识点：检修后送电前须确认防爆性能完好、绝缘电阻合格，才能恢复送电。错误项：测外壳温度不能反映检修质量；清点工具与送电条件无关；外观油漆不影响电气安全但非送电前必检项。"},{"id":191,"type":"single","stem":"井下电气设备的防爆标志中，表示隔爆型的符号是","options":["本安型标志符号","增安型标志符号","隔爆型标志符号","正压型标志符号"],"answer":[2],"explanation":"知识点：隔爆型电气设备的防爆标志用特定符号标注，代表外壳能承受内部爆炸而不传爆。错误项：本安型靠限制能量实现防爆；增安型靠提高安全裕度；正压型靠保持正压，三者均与隔爆外壳原理不同。"},{"id":192,"type":"single","stem":"井下电气作业中，验电器的使用顺序正确的是","options":["先验高压后验低压最后验地","先在带电体上试验再验电","先验电后在有电处试验其完好","只需验电无需试验验电器"],"answer":[2],"explanation":"知识点：验电器使用前应在有电部位试验其完好，再对停电设备验电，确认无电后方可作业。错误项：先验高压顺序无依据；未试验直接验电可能因验电器损坏误判；不试验验电器无法确认其可靠性。"},{"id":193,"type":"single","stem":"井下局部通风机因故障停风后恢复通风前，电气作业人员应优先确认的是","options":["通风机电机绝缘电阻值","停风区域瓦斯浓度是否超限","通风机轴承润滑是否良好","通风机电源电压是否稳定"],"answer":[1],"explanation":"知识点：停风区域可能积聚瓦斯，恢复通风前必须先检查瓦斯浓度，超限时不得送电，防止送电火花引爆。错误项：电机绝缘、轴承润滑、电压稳定是通风机本身状态，但不能替代瓦斯检查这一安全前提。"},{"id":194,"type":"single","stem":"井下电气设备运行中闻到焦糊味且外壳温度异常升高，正确的处置是","options":["继续运行并加强通风降温","立即停电检查并排除故障","降低负荷继续观察运行","记录现象待检修班处理"],"answer":[1],"explanation":"知识点：焦糊味和异常温升是过载、短路或接触不良的征兆，应立即停电检查，防止火灾或引爆瓦斯。错误项：继续运行或降负荷观察会延误处理；仅记录待处理会使故障扩大。"},{"id":195,"type":"multi","stem":"井下电气设备停电检修时，属于必须执行的安全措施有","options":["切断电源并悬挂停电警示牌","验电确认无电后放电","在可能反送电处装设接地线","检修完毕清点工具后送电","用湿抹布擦拭带电母线"],"answer":[0,1,2],"explanation":"知识点：停电检修须执行停电、验电、放电、装设接地线、挂牌等安全措施。错误项：清点工具是检修结束的整理工作，不是停电安全措施；用湿抹布擦拭带电母线属严重违章，会触电。"},{"id":196,"type":"single","stem":"井下低压馈电开关中，漏电闭锁与漏电保护的主要区别是","options":["漏电闭锁动作于跳闸，漏电保护动作于闭锁","漏电闭锁在合闸前检测绝缘并闭锁，漏电保护在运行中检测并跳闸","漏电闭锁只用于高压，漏电保护只用于低压","漏电闭锁由人工复位，漏电保护自动复位"],"answer":[1],"explanation":"知识点：漏电闭锁与漏电保护的功能区分。漏电闭锁是在开关合闸前检测负载侧绝缘电阻，低于规定值就闭锁不能合闸；漏电保护是运行中检测到漏电电流后动作跳闸。前者防合闸于故障线路，后者防运行中漏电事故。"},{"id":197,"type":"single","stem":"井下电气设备运行中发出异常糊味且外壳温度明显升高，正确的处置是","options":["加强通风降温后继续运行","立即停机断电检查处理","记录温度变化继续观察","降低负荷后继续运行"],"answer":[1],"explanation":"知识点：电气设备异常运行处置。糊味和温升异常说明绝缘可能过热损坏，应立即停机断电检查；通风降温、继续观察、降负荷运行都可能使故障扩大引发火灾或漏电。"},{"id":198,"type":"single","stem":"井下电缆与电气设备连接时，电缆芯线与接线端子的连接方式应采用","options":["芯线绕接线柱一圈后拧紧","芯线插入接线端子用卡爪或螺栓压紧","芯线绞接后塞入端子孔","芯线搭接在端子上用胶带绑扎"],"answer":[1],"explanation":"知识点：电缆芯线与端子连接要求。应插入端子用卡爪或螺栓压紧保证接触良好；绕一圈接触面小易发热；绞接塞入接触不可靠；搭接绑扎不符合连接要求且易脱落。"},{"id":199,"type":"single","stem":"井下变电所内检修高压电气设备时，安全措施中停电操作的正确顺序是","options":["先拉负荷侧隔离开关再拉电源侧","先拉断路器再拉负荷侧和电源侧隔离开关","先拉电源侧隔离开关再拉负荷侧","只拉断路器即可开始检修"],"answer":[1],"explanation":"知识点：高压停电操作顺序。必须先拉断路器切断负荷电流，再拉负荷侧隔离开关，最后拉电源侧隔离开关；带负荷拉隔离开关会产生电弧引发事故；只拉断路器未隔离电源仍有来电危险。"},{"id":200,"type":"single","stem":"井下某掘进工作面局部通风机突然停风，瓦斯检查工检查后确认停风区瓦斯浓度达到1.5%，此时电气作业人员的正确做法是","options":["立即启动局部通风机恢复通风","保持停风区电气设备停电闭锁并撤出人员","送电启动排水泵后等待恢复通风","打开风筒接头用自然风稀释瓦斯"],"answer":[1],"explanation":"知识点：停风区瓦斯超限时的电气安全处置。瓦斯浓度达1.5%时严禁送电和启动设备，必须保持停电闭锁、撤出人员、设置警戒；直接启动风机可能造成瓦斯涌出事故；送电排水违反停电闭锁规定；自然风稀释不可靠且违反规程。"},{"id":201,"type":"single","stem":"井下电气设备隔爆外壳上的紧固螺栓，在检修后复装时应当如何处置","options":["全部装齐并逐条拧紧至弹簧垫圈压平","隔一条装一条以节省检修时间","缺失的螺栓用同直径普通螺栓代替","螺栓拧至用手拧不动即可不再加力"],"answer":[0],"explanation":"知识点：隔爆外壳紧固螺栓必须齐全并可靠紧固，否则失去隔爆性能。正确项装齐并拧紧至弹簧垫圈压平，能保证外壳结合面压紧、间隙符合隔爆要求。隔一条装一条会减少压紧点使结合面间隙超标；用普通螺栓代替会因强度或螺纹精度不足导致隔爆失效；只用手拧不动不加力则压紧力不够。"},{"id":202,"type":"single","stem":"井下检漏保护装置动作使馈电开关跳闸后，未查明原因前对该开关的正确处置是","options":["试送一次观察是否再跳","甩掉检漏保护后送电","把检漏整定值调大后送电","保持停电并查找漏电点"],"answer":[3],"explanation":"知识点：漏电闭锁与检漏保护动作后必须查明原因、排除故障方可送电。正确项保持停电并查找漏电点，符合先排查后送电的原则。试送一次可能扩大事故；甩掉保护属于擅自退出保护；调大整定值掩盖了真实漏电，都可能造成人身触电或引爆。"},{"id":203,"type":"single","stem":"井下低压电缆与风水管路同侧敷设时，电缆应布置在管路的哪个位置","options":["管路正上方且紧贴管壁","管路下方并保持规定间距","与管路同一水平并排紧靠","管路正上方并留出检修空间"],"answer":[0],"explanation":"知识点：井下电缆应与风水管路分侧或保持规定间距，同侧敷设时电缆应在管路上方并保持间距，防止管路漏水或维修伤及电缆。正确项体现了在上方的要求。放在管路下方、同水平紧靠，都易受管路滴漏水或检修碰撞影响；在正上方但留检修空间的表述与本条要求相比不完整，管路在上方时才是电缆应处的相对位置要求的准确表达。"},{"id":204,"type":"single","stem":"掘进工作面局部通风机因故停止运转后，对掘进巷道内电气设备的正确处置是","options":["保持送电等待风机恢复","切断巷道内动力电源","只切断照明回路电源","将设备转为检修状态"],"answer":[1],"explanation":"知识点：局部通风机停风后，掘进巷道内瓦斯可能积聚，必须切断巷道内动力电源、撤出人员。正确项切断动力电源可防止电气火花引爆积聚瓦斯。保持送电可能因设备运行产生火花；只切照明不切动力不能消除主要点火源；转检修状态并未切断巷道动力电源。"},{"id":205,"type":"single","stem":"井下用摇表测量电缆绝缘电阻时，测量结束后对电缆芯线的正确操作是","options":["立即用手触摸芯线放电","先断开摇表再直接拆线","先对地放电再拆线","保持摇表连接等待自然放电"],"answer":[2],"explanation":"知识点：摇表测量后电缆芯线上存有残余电荷，必须先对地放电再拆线，防止电击。正确项为先对地放电再拆线。立即触摸芯线会遭残余电荷电击；先断开摇表再直接拆线未放电同样有电击风险；保持连接等待自然放电耗时且不可靠。"},{"id":206,"type":"single","stem":"井下电气设备隔爆结合面上涂覆防锈油时，正确的做法是","options":["涂一层薄防锈油并防止流入内部","涂厚层黄油以增强密封效果","涂普通机油并允许渗入壳内","结合面保持干燥不涂任何油脂"],"answer":[0],"explanation":"知识点：隔爆结合面可涂薄层防锈油防锈，但不得影响隔爆间隙且不能流入壳内。正确项为涂薄防锈油。涂厚黄油会改变结合面间隙；机油渗入壳内可能影响绝缘或与内部介质反应；完全不涂易生锈损坏结合面精度，均不符合要求。"},{"id":207,"type":"single","stem":"井下电缆连接采用冷补法时，对芯线连接的基本要求是","options":["芯线绞接后直接包缠绝缘","芯线压接或焊接后包缠绝缘","芯线扭结后灌胶固定","芯线搭接后用胶带压紧"],"answer":[1],"explanation":"知识点：电缆冷补时芯线应采用压接或焊接等可靠连接方式，再恢复绝缘和护套。正确项为压接或焊接后包缠绝缘。单纯绞接、扭结、搭接后包缠，接触电阻大、易发热，不能满足井下供电可靠性要求。"},{"id":208,"type":"single","stem":"井下电气设备运行中出现外壳温度异常升高但未超过规定值时，正确的处置是","options":["继续运行并加强观察","立即停电检查原因","降低负荷继续运行","打开外壳通风散热"],"answer":[1],"explanation":"知识点：设备温度异常升高往往是内部故障的前兆，应停电检查。正确项为立即停电检查。继续运行或降负荷运行可能使故障扩大；打开外壳通风会破坏隔爆性能并可能触及带电部分，均属错误处置。"},{"id":209,"type":"single","stem":"井下变电所内检修高压开关时，验电环节的正确操作顺序是","options":["先验电再放电最后挂接地线","先挂接地线再验电放电","先放电再验电后挂接地线","先验电后挂接地线不放电"],"answer":[0],"explanation":"知识点：高压检修停电后应验电、放电、挂接地线。正确项顺序为先验电再放电最后挂接地线。先挂接地线再验电可能因残余电荷伤人；先放电再验电顺序颠倒，未验电无法确认是否带电；不放电直接挂接地线同样有残余电荷风险。"},{"id":210,"type":"single","stem":"井下移动变电站低压侧馈电开关的漏电闭锁功能，其作用是在什么情况下闭锁开关","options":["开关合闸后检测到漏电","开关合闸前检测到漏电","运行中电流超过整定值","运行中电压低于额定值"],"answer":[1],"explanation":"知识点：漏电闭锁是在开关合闸前检测负载侧绝缘，若绝缘低于规定值则闭锁，不允许合闸。正确项为合闸前检测到漏电。合闸后检测到漏电属于漏电保护动作跳闸；电流超整定是过流保护；电压低是欠压保护，均不是漏电闭锁的作用。"},{"id":211,"type":"multi","stem":"井下电气作业中，下列哪些做法符合隔爆电气设备检修后的送电条件","options":["隔爆外壳紧固螺栓齐全并压紧","接线嘴密封圈与电缆外径紧密配合","保护装置整定值按原设计恢复","用普通螺栓代替缺失的隔爆螺栓","检漏保护暂时甩掉以便试送电"],"answer":[0,1,2],"explanation":"知识点：隔爆设备送电前应确认外壳紧固、密封良好、保护整定正确。正确项为螺栓齐全压紧、密封圈紧密配合、整定值恢复。用普通螺栓代替隔爆螺栓会降低隔爆性能；甩掉检漏保护送电会失去漏电保护，均不允许。"},{"id":212,"type":"single","stem":"井下电气设备隔爆外壳失去隔爆性能的主要判断依据是","options":["外壳表面有明显锈蚀但隔爆面完好","隔爆面有轻微划痕但宽度未超标","隔爆面出现凹坑或间隙超过规定值","外壳紧固螺栓缺少一个但其余紧固"],"answer":[2],"explanation":"知识点：隔爆外壳完好标准。正确项对在隔爆面凹坑或间隙超限会直接破坏隔爆性能。A项错在锈蚀不在隔爆面上不影响隔爆；B项错在轻微划痕未超宽仍可使用；D项错在缺螺栓使外壳紧固力不足但题干问的是隔爆面本身失效的主要依据。"},{"id":213,"type":"single","stem":"井下电缆连接时，不同截面的电缆进行冷压连接的正确做法是","options":["两电缆截面差不超过一档时可直接压接","必须使用与较小截面电缆匹配的连接管","必须使用与较大截面电缆匹配的连接管","截面不同时禁止任何形式的连接"],"answer":[1],"explanation":"知识点：电缆冷压连接管选配。正确项对在连接管应与较小截面电缆匹配以保证压紧。A项错在截面差一档仍需专用连接管过渡；C项错在用大截面连接管压小截面电缆会压不实；D项错在截面不同可通过合格连接管连接并非绝对禁止。"},{"id":214,"type":"single","stem":"井下低压馈电开关的漏电闭锁功能应在什么状态下起作用","options":["开关合闸后检测到漏电时跳闸","开关合闸前检测到漏电时闭锁不能合闸","开关运行中每班手动检测一次","漏电电流超过整定值后延时跳闸"],"answer":[1],"explanation":"知识点：漏电闭锁与漏电保护的区别。正确项对在漏电闭锁是在合闸前检测到漏电即闭锁，防止带故障合闸。A项错在合闸后跳闸属于漏电保护动作；C项错在手动检测不是闭锁功能；D项错在延时跳闸描述的是过流保护特性。"},{"id":215,"type":"single","stem":"井下检漏继电器动作后，正确的处置程序是","options":["直接复位后继续送电观察","查明漏电原因并处理后才能复位送电","将检漏继电器退出运行后送电","调整漏电整定值后复位送电"],"answer":[1],"explanation":"知识点：检漏继电器动作后处置。正确项对在必须查明原因处理后方可复位送电。A项错在直接复位可能带故障送电；C项错在退出检漏运行属严重违章；D项错在擅自调整整定值掩盖故障。"},{"id":216,"type":"single","stem":"井下电气设备隔爆接合面的紧固螺栓正确安装方式是","options":["螺栓拧紧后弹簧垫圈压平即可","螺栓伸入孔内不少于螺母厚度即可","螺栓须拧紧且弹簧垫圈不得压平","螺栓可加装平垫代替弹簧垫圈"],"answer":[2],"explanation":"知识点：隔爆外壳紧固螺栓要求。正确项对在螺栓须拧紧且弹簧垫圈保持弹性不得压平。A项错在弹簧垫圈压平说明紧固力可能过大或失效；B项错在伸入长度不是隔爆紧固的核心判据；D项错在平垫无防松作用不能替代弹簧垫圈。"},{"id":217,"type":"single","stem":"井下使用摇表测量电缆绝缘电阻时，正确的操作顺序是","options":["先接摇表再摇动手柄最后读数","先摇动手柄达到额定转速再接被测电缆","先断开电缆两端再接线摇测读数","先放电再接线摇动手柄读数后放电"],"answer":[3],"explanation":"知识点：摇表测绝缘操作程序。正确项对在测前放电、测后放电是完整程序。A项错在未先放电就接线有残余电荷风险；B项错在带电接线可能损坏摇表；C项错在缺少测后放电环节。"},{"id":218,"type":"single","stem":"井下电气设备运行中闻到焦糊味且外壳温度明显升高，值班电工首先应","options":["加强通风降温后继续观察运行","立即停机并断开电源检查","记录温度变化待交接班处理","降低负荷后维持运行"],"answer":[1],"explanation":"知识点：电气设备异常温升处置。正确项对在焦糊味加高温是故障征兆须立即停机断电。A项错在继续运行可能引发火灾；C项错在拖延处置扩大故障；D项错在降负荷不消除内部故障。"},{"id":219,"type":"single","stem":"井下采掘工作面电气设备搬迁时，正确的停电范围是","options":["只停被搬迁设备本身的电源","停被搬迁设备及其负荷侧所有电源","停采区变电所全部出线电源","停被搬迁设备电源并验电挂牌"],"answer":[3],"explanation":"知识点：设备搬迁停电安全措施。正确项对在停本设备电源并验电挂牌是完整程序。A项错在只停电不验电挂牌不完整；B项错在扩大停电范围影响其他设备；C项错在停全采区出线属过度停电。"},{"id":220,"type":"multi","stem":"井下电气作业中，下列属于必须立即停电处理的情形有","options":["隔爆外壳发现裂纹","电缆护套局部破损露出芯线","设备运行声音略有增大","接地线连接螺栓轻微锈蚀"],"answer":[0,1],"explanation":"知识点：电气设备必须立即停电的缺陷判断。A项对在隔爆外壳裂纹直接丧失隔爆性能；B项对在护套破损露芯线有短路和触电风险。C项错在声音略增大可加强监视不一定要立即停电；D项错在螺栓轻微锈蚀可除锈紧固不必立即停电。"},{"id":221,"type":"single","stem":"井下电气设备隔爆外壳上的隔爆接合面出现轻微锈蚀时，正确的处理方法是","options":["用砂纸打磨除锈后涂防锈油","用棉纱擦净后涂薄层凡士林","刮刀刮净锈层后立即装配","用钢丝刷除锈后保持干燥"],"answer":[1],"explanation":"知识点：隔爆接合面的维护要求。隔爆接合面轻微锈蚀应用棉纱擦净后涂薄层凡士林防锈，不能改变接合面间隙。用砂纸打磨会改变间隙超差，故A错；刮刀刮净会损伤接合面平整度，故C错；钢丝刷除锈会划伤接合面，故D错。"},{"id":222,"type":"single","stem":"井下检漏继电器在电网绝缘电阻低于整定值时，其正确动作结果是","options":["发出声光报警但不断开主回路","立即切断被保护线路电源并闭锁","延时30秒后切断被保护线路电源","仅断开漏电线路的负荷侧开关"],"answer":[1],"explanation":"知识点：检漏继电器的保护动作方式。检漏继电器检测到绝缘电阻低于整定值时应立即切断被保护线路电源并闭锁，防止漏电引发事故。A项只报警不断电无法起到保护作用；C项延时会扩大触电危险；D项只断负荷侧不能隔离漏电点。"},{"id":223,"type":"single","stem":"井下电气设备防爆检查中，隔爆外壳上的紧固螺栓缺少弹簧垫圈时，该设备应判定为","options":["不影响防爆性能，可以继续使用","防爆性能合格但需限期补齐","失去防爆性能，禁止使用","仅需在检修记录中注明即可"],"answer":[2],"explanation":"知识点：隔爆外壳紧固件的防爆要求。弹簧垫圈是防止螺栓松动、保证隔爆间隙的关键零件，缺少后外壳可能松动导致隔爆性能丧失。A项和B项低估了紧固件缺失的后果；D项仅记录不处理不能恢复防爆性能。"},{"id":224,"type":"single","stem":"井下电缆连接时，两根电缆的芯线采用压接法连接后，对接头处的绝缘处理正确做法是","options":["缠绕绝缘胶带后套热缩管加热收缩","直接套上冷缩管自然恢复即可","缠绕绝缘胶带后涂绝缘漆晾干","套上塑料套管后用扎带固定"],"answer":[0],"explanation":"知识点：井下电缆接头绝缘恢复工艺。正确做法是缠绕绝缘胶带后套热缩管加热收缩，保证绝缘强度和密封性。B项冷缩管在井下潮湿环境密封不可靠；C项涂绝缘漆晾干无法保证绝缘层厚度和密封；D项塑料套管加扎带不具备绝缘恢复功能。"},{"id":225,"type":"single","stem":"井下移动变电站低压侧馈电开关的漏电闭锁功能，其作用是","options":["在开关合闸前检测线路绝缘并闭锁","在开关运行中检测漏电并跳闸","在开关分闸后自动放电","在开关合闸后延时投入漏电保护"],"answer":[0],"explanation":"知识点：漏电闭锁与漏电保护的区别。漏电闭锁是在开关合闸前检测线路绝缘，绝缘不合格则闭锁不能合闸。B项是漏电保护的功能（运行中跳闸）；C项是放电装置的功能；D项描述与漏电闭锁动作时机不符。"},{"id":226,"type":"single","stem":"井下电气设备接地网上，接地电阻值的测定周期要求是","options":["每季度至少测定一次","每半年至少测定一次","每年至少测定一次","每两年至少测定一次"],"answer":[0],"explanation":"知识点：井下接地网接地电阻测定周期。按规定接地电阻每季度至少测定一次，确保接地系统有效。B项半年周期过长；C项一年不符合季度测定要求；D项两年更不符合规定。"},{"id":227,"type":"single","stem":"井下电气维修人员在检修开关时，将停电开关的操作手柄锁住并悬挂\"有人工作，禁止合闸\"标示牌，这一措施属于","options":["停电措施","验电措施","闭锁措施","放电措施"],"answer":[2],"explanation":"知识点：检修安全技术措施的分类。锁住操作手柄并悬挂标示牌属于闭锁措施，防止误合闸。A项停电是切断电源本身；B项验电是确认无电；D项放电是对储能元件释放电荷。"},{"id":228,"type":"single","stem":"井下掘进工作面局部通风机因故障停风后，瓦斯检查工测得停风区瓦斯浓度为1.5%，此时对局部通风机及其开关附近电气设备的正确处置是","options":["立即人工启动局部通风机恢复通风","先检查瓦斯再决定是否送电","保持停风状态并切断电源撤出人员","打开风筒接口自然通风后送电"],"answer":[2],"explanation":"知识点：停风后瓦斯超限时的电气设备处置。停风区瓦斯浓度达到1.5%时，必须保持停风状态、切断电源、撤出人员，等待恢复通风措施。A项未检查瓦斯就启动风机可能引发爆炸；B项瓦斯已超限不能简单检查后送电；D项自然通风不可靠且送电有爆炸风险。"},{"id":229,"type":"single","stem":"井下某采区变电所一台馈电开关频繁跳闸，维修人员到达后正确的排查步骤是","options":["先检查漏电保护整定值再查负荷侧绝缘","先断开负荷侧开关再逐段排查线路","先更换开关本体再观察是否跳闸","先调大过流整定值再试送电"],"answer":[1],"explanation":"知识点：馈电开关频繁跳闸的排查程序。正确做法是先断开负荷侧开关，逐段排查线路，缩小故障范围。A项先查整定值可能忽略真实故障点；C项直接换开关本体盲目且可能掩盖线路故障；D项调大整定值会失去保护作用且违章。"},{"id":230,"type":"single","stem":"井下电气设备进行检修时，验电后确认无电，接下来应优先执行的操作是","options":["对地放电并挂接地线","直接开始拆卸接线腔","测量绝缘电阻确认无电","挂牌后通知调度开始作业"],"answer":[0],"explanation":"知识点：检修停电安全程序。验电只能确认当时无电，但电缆和电容元件可能残存电荷，必须先对地放电并三相短接接地，才能防止残余电荷伤人。B项直接拆卸会在残存电荷未释放时触电；C项测绝缘电阻不能替代放电接地，且万用表测量不构成安全措施；D项挂牌通知是后续管理步骤，缺少放电接地这一关键环节。"},{"id":231,"type":"single","stem":"井下低压馈电开关的漏电闭锁功能，其作用是","options":["开关合闸前检测线路绝缘并闭锁合闸","运行中检测漏电电流并延时跳闸","检测短路电流并瞬时跳闸","检测过载电流并反时限跳闸"],"answer":[0],"explanation":"知识点：漏电闭锁与漏电保护的区别。漏电闭锁是在开关合闸前对负载侧绝缘进行检测，绝缘不合格时闭锁合闸，防止向故障线路送电。B项描述的是漏电保护（运行中跳闸）的动作方式；C项是短路保护功能；D项是过载保护功能，三者均与合闸前闭锁无关。"},{"id":232,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面涂油时，正确做法是","options":["涂薄层防锈油且不得涂入结合面间隙","涂满润滑脂以增强密封效果","涂油漆防止结合面锈蚀","涂导电膏降低接触电阻"],"answer":[0],"explanation":"知识点：隔爆结合面维护要求。隔爆结合面需要保持规定的间隙和粗糙度，只能涂薄层防锈油，且不能把油涂进间隙内，否则会改变隔爆间隙参数、影响隔爆性能。B项涂满润滑脂会堵塞间隙、改变隔爆参数；C项涂油漆会改变结合面尺寸并可能脱落；D项涂导电膏无必要且会污染结合面，均错误。"},{"id":233,"type":"single","stem":"井下电缆连接时，若发现橡套电缆的屏蔽层在冷补接头处断开，正确的处置是","options":["重新制作接头并恢复屏蔽层连接","用绝缘胶带缠绕屏蔽层断口","将屏蔽层两端分别接地即可","在断口处灌注绝缘胶封闭"],"answer":[0],"explanation":"知识点：屏蔽电缆接头工艺要求。屏蔽层的作用是均衡电场、限制电位，接头处必须连续恢复连接，断开会导致局部电场集中、绝缘老化甚至击穿，因此应重新制作接头。B项缠绕胶带不能恢复电气连续性；C项两端接地会造成环流且中断屏蔽连续性；D项灌注绝缘胶无法恢复屏蔽功能，均不合要求。"},{"id":234,"type":"single","stem":"井下电气作业中，使用普通万用表测量馈电开关负荷侧电压前，必须确认的首要条件是","options":["验电确认无电并放电接地","万用表档位打到交流电压档","戴好绝缘手套站在绝缘台上","通知调度后开始测量"],"answer":[0],"explanation":"知识点：停电检修测量的安全前提。测量负荷侧电压通常属于检修后验证或故障排查，必须先验电、放电、接地，确保无电才能接触或测量，否则可能触电。B项选档位是操作细节，不能保证人身安全；C项防护用品不能替代停电措施；D项通知调度是管理程序，不是首要安全条件。"},{"id":235,"type":"single","stem":"井下移动变电站低压侧馈电开关频繁出现漏电闭锁，排查时首先应检查的部位是","options":["负荷侧电缆及用电设备绝缘状况","开关内部合闸线圈是否烧损","上级高压开关的整定值","变压器油位是否正常"],"answer":[0],"explanation":"知识点：漏电闭锁动作原因分析。漏电闭锁反映负荷侧绝缘不合格，因此首先应检查负荷侧电缆和用电设备的绝缘。B项合闸线圈故障表现为不能合闸，与漏电闭锁信号不同；C项上级整定值影响过流保护，不直接引起漏电闭锁；D项变压器油位影响变压器运行，与低压侧漏电闭锁无直接关系。"},{"id":236,"type":"single","stem":"井下防爆电气设备接线时，电缆护套伸入接线腔的长度要求是","options":["护套应伸入接线腔内壁5至15毫米","护套应与接线腔内壁平齐","护套应伸出接线腔内壁20毫米","护套留在接线腔外即可"],"answer":[0],"explanation":"知识点：防爆接线工艺要求。电缆护套需伸入接线腔内壁5至15毫米，既能防止电缆芯线绝缘受损，又能保证密封和隔爆性能。B项平齐易造成芯线绝缘在腔口处磨损；C项伸出过长会占用腔内空间、影响爬电距离；D项留在腔外则密封圈无法有效密封，均不符合要求。"},{"id":237,"type":"single","stem":"井下电气设备运行中，检漏继电器动作使馈电开关跳闸，在未查明原因前正确的处置是","options":["允许试送一次以判断是否误动作","将检漏继电器退出后强制送电","短接检漏继电器接点后送电","改用手动方式合闸送电"],"answer":[0],"explanation":"知识点：漏电保护动作后的处置原则。检漏继电器动作后，在未查明原因前，允许试送一次以判断是否为瞬时性误动作，但不得退出或短接保护。B项退出检漏继电器会使线路失去漏电保护；C项短接接点等于取消保护；D项手动合闸同样绕过了漏电闭锁，均属严重违章。"},{"id":238,"type":"single","stem":"井下电气设备隔爆外壳的观察窗玻璃损坏后，正确的更换要求是","options":["更换同规格的钢化玻璃并压紧密封","用普通平板玻璃临时替换","用透明塑料板代替并密封","用金属盲板封堵后继续使用"],"answer":[0],"explanation":"知识点：隔爆外壳观察窗的维修要求。观察窗玻璃必须使用规定强度的钢化玻璃，并保证密封和压紧，才能维持隔爆性能。B项普通平板玻璃强度不足，受压易碎；C项塑料板不耐温、不耐压且不具隔爆强度；D项金属盲板封堵会失去观察功能，且未经设计认可不能随意改变外壳结构，均不正确。"},{"id":239,"type":"single","stem":"井下电气作业中，检修完毕后恢复送电前，必须完成的关键步骤是","options":["拆除接地线并清点工具、人员撤离","直接合闸试送电观察设备运行","先送电再拆除接地线","通知调度后立即合闸送电"],"answer":[0],"explanation":"知识点：恢复送电前的安全确认。送电前必须拆除全部接地线、清点工具和人员、确认无人作业，防止带接地线合闸或遗留工具造成事故。B项直接合闸可能带接地线送电；C项先送电再拆接地线会形成短路；D项仅通知调度不能替代现场安全确认，均错误。"},{"id":240,"type":"single","stem":"井下电气设备隔爆外壳的隔爆面有轻微锈蚀，检修时正确的处理方式是","options":["用棉纱擦净后涂防锈油","用砂纸打磨至露出金属光泽","用钢丝刷除锈后涂凡士林","用刮刀刮平后直接装配"],"answer":[0],"explanation":"知识点：隔爆面维护要求。隔爆面轻微锈蚀只需擦净并涂防锈油，保持隔爆间隙和表面粗糙度；用砂纸打磨会改变间隙、破坏隔爆性能；钢丝刷除锈会划伤隔爆面；刮刀刮平会减小间隙，均不符合要求。"},{"id":241,"type":"single","stem":"井下检漏继电器每月应进行的试验是","options":["远方人工漏电跳闸试验","绝缘电阻摇测试验","接地电阻测量试验","耐压击穿试验"],"answer":[0],"explanation":"知识点：检漏继电器日常试验项目。检漏继电器每月应做一次远方人工漏电跳闸试验，验证动作可靠性；绝缘电阻摇测、接地电阻测量属其他项目；耐压试验属高压设备预防性试验，与检漏继电器月试无关。"},{"id":242,"type":"single","stem":"井下电气设备接线嘴与电缆之间密封圈的单孔内径与电缆外径之差应满足","options":["不大于1毫米","不大于2毫米","不大于3毫米","不大于5毫米"],"answer":[0],"explanation":"知识点：密封圈与电缆配合间隙。密封圈单孔内径与电缆外径之差不得大于1毫米，才能保证密封和隔爆性能；2、3、5毫米间隙过大，失爆风险高，不符合隔爆要求。"},{"id":243,"type":"single","stem":"井下低压馈电开关的过流保护整定值确定后，运行中需要调整时应当","options":["由值班电工按经验直接调整","由专职电气人员核算后调整","由班组长根据负荷情况调整","由配电工参照同类开关调整"],"answer":[1],"explanation":"知识点：过流保护整定管理。整定值需由专职电气人员根据负荷计算、校验后调整，确保选择性；值班电工凭经验、班组长凭负荷、配电工参照同类调整均缺乏计算依据，可能造成误动或拒动。"},{"id":244,"type":"single","stem":"井下电气设备停电检修时，验电环节的正确做法是","options":["用电压等级相符的验电器在停电设备各相分别验电","用低压验电笔在设备外壳上验电","用万用表在开关出线侧测量验电","用绝缘手套触摸接线端子判断有无电"],"answer":[0],"explanation":"知识点：停电检修验电要求。应用电压等级相符的验电器在停电设备各相分别验电，确认无电；验电笔在壳上验电不能反映内部带电；万用表测出线侧不能代替验电；用手触摸极其危险且违规。"},{"id":245,"type":"single","stem":"井下移动变电站低压侧漏电保护动作后，排查故障前应当先","options":["直接复位试送电观察是否再跳","将低压侧总开关断开并挂牌","拉开高压侧隔离开关即可","测量负荷侧绝缘电阻后送电"],"answer":[1],"explanation":"知识点：漏电保护动作后处置程序。应先断开低压侧总开关并挂牌，防止误送电；直接复位试送会扩大故障；仅拉高压侧隔离开关不能确保低压侧无电；未查明原因即测绝缘送电不符合程序。"},{"id":246,"type":"single","stem":"井下电气设备运行中听到内部有异常放电声，正确的处置是","options":["继续运行并加强监视","立即停电检查并汇报","降低负荷后继续观察","记录声音间隔后再决定"],"answer":[1],"explanation":"知识点：异常放电处置。内部放电声说明绝缘可能击穿，应立即停电检查并汇报；继续运行、降负荷观察、记录间隔后再决定都会延误处置，可能引起短路或火灾。"},{"id":247,"type":"single","stem":"井下某掘进工作面局部通风机电源开关突然跳闸，恢复送电前应当先","options":["直接合闸试送电观察风机是否启动","检查开关保护动作原因并排除故障","将风机开关打到手动位置试送","通知工作面人员撤出后送电"],"answer":[1],"explanation":"知识点：局部通风机停电处置。跳闸后应先检查保护动作原因、排除故障再送电；直接合闸可能再次跳闸或损坏设备；打手动试送不查原因；通知撤人但未查故障，仍不能安全送电。"},{"id":248,"type":"single","stem":"井下电气设备隔爆结合面的紧固螺栓在检修后应当","options":["齐全、紧固，弹簧垫圈压平","齐全，用手拧紧即可","缺一个不影响时可不补","紧固但可不加弹簧垫圈"],"answer":[0],"explanation":"知识点：隔爆外壳紧固要求。紧固螺栓应齐全、紧固，弹簧垫圈压平，保证隔爆面压紧；手拧紧力矩不足；缺螺栓会降低隔爆性能；不加弹簧垫圈易松动，均不符合要求。"},{"id":249,"type":"multi","stem":"井下电气设备发生漏电故障后，在恢复送电前应当完成的工作有","options":["查明漏电原因并处理","测量漏电设备及电缆绝缘电阻","检查检漏继电器动作是否可靠","直接复位漏电闭锁后试送电","用兆欧表测量接地电阻"],"answer":[0,1,2],"explanation":"知识点：漏电故障恢复送电条件。应查明原因并处理、测量绝缘电阻、检查检漏继电器动作可靠性；直接复位试送电未排除故障；测接地电阻不是漏电故障恢复送电前的必做项目。"},{"id":250,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并处理前，对该供电回路应采取的措施是","options":["可试送一次观察","允许合闸试运行","禁止强行送电","断开负荷后送电"],"answer":[2],"explanation":"知识点：漏电闭锁与故障处理。检漏动作说明绝缘可能损坏，未查明原因强行送电可能引发触电或瓦斯爆炸，必须禁止强行送电；试送、试运行、断负荷送电都属强行送电的变相做法，均不安全。"},{"id":251,"type":"single","stem":"矿用隔爆型电气设备接线时，密封圈内径与电缆外径的配合要求是","options":["密封圈内径略大于电缆外径","密封圈内径略小于电缆外径","密封圈内径与电缆外径相符","密封圈内径按电缆外径加一档"],"answer":[2],"explanation":"知识点：电缆引入装置密封要求。密封圈内径应与电缆外径相符才能保证压紧后密封；内径过大会漏气失爆，内径过小会割伤电缆，加一档选配同样造成间隙过大失爆。"},{"id":252,"type":"single","stem":"井下电气设备检修需要停电时，验电、放电之后还应进行的工作是","options":["挂接地线","挂牌上锁","装设遮栏","悬挂标示牌"],"answer":[0],"explanation":"知识点：停电检修安全措施顺序。验电、放电后必须挂接地线，防止突然来电和感应电伤人；挂牌上锁是防止误送电的管理措施，遮栏和标示牌是警示隔离措施，均不能替代接地线。"},{"id":253,"type":"single","stem":"井下运行中的电气设备外壳出现温度异常升高，最应先做的处置是","options":["加强通风降温","停电检查原因","降低负荷运行","涂散热硅脂"],"answer":[1],"explanation":"知识点：设备过热异常判断。外壳异常发热可能是内部接触不良、过载或短路，应停电检查；加强通风、降负荷、涂硅脂都只是掩盖现象，不停电检查可能酿成火灾或失爆。"},{"id":254,"type":"single","stem":"矿用电缆在井下巷道内悬挂时，电缆与风水管路的相对位置要求是","options":["电缆挂在管路上方","电缆挂在管路下方","电缆与管路同侧平行","电缆可任意挂设"],"answer":[0],"explanation":"知识点：井下电缆悬挂规定。电缆应挂在管路上方，防止管路漏水淋湿电缆或管路检修时损伤电缆；挂在下方易受潮，同侧平行易受碰撞，任意挂设违反规定。"},{"id":255,"type":"single","stem":"井下隔爆型电动机运行中出现剧烈振动并伴有异响，正确的下一步操作是","options":["立即停电检查","降速继续观察","紧固地脚螺栓","加注润滑油"],"answer":[0],"explanation":"知识点：电动机异常振动判断。剧烈振动加异响可能是轴承损坏、转子扫膛或地脚松动，应立即停电检查；降速、紧固、加油都可能延误处理导致设备损坏或引发事故。"},{"id":256,"type":"single","stem":"井下检漏继电器与馈电开关配合使用时，检漏继电器动作后馈电开关应","options":["延时跳闸","立即跳闸","报警不跳闸","手动跳闸"],"answer":[1],"explanation":"知识点：漏电保护配合。检漏继电器动作后应使馈电开关立即跳闸切断电源；延时跳闸扩大触电危险，只报警不跳闸失去保护作用，手动跳闸不能自动切断电源。"},{"id":257,"type":"single","stem":"井下电气作业中，操作高压设备时正确的做法是","options":["戴绝缘手套并站在绝缘台上","戴棉纱手套单手操作","戴绝缘手套直接操作","站绝缘台上不戴手套操作"],"answer":[0],"explanation":"知识点：高压操作安全防护。操作高压设备须戴绝缘手套并站在绝缘台上，双重防护；棉纱手套无绝缘作用，仅戴手套或仅站绝缘台都缺少一道防护。"},{"id":258,"type":"single","stem":"井下某掘进工作面局部通风机突然停风，瓦斯检查工不在现场，电气作业人员的正确处置是","options":["立即撤离并断电","等待瓦斯检查后再决定","继续作业尽快完工","通知班长后继续作业"],"answer":[0],"explanation":"知识点：停风撤人规定。停风后可能积聚瓦斯，电气作业人员应立即撤离并切断电源；等待检查、继续作业、通知班长后继续都可能遇瓦斯超限引发爆炸。"},{"id":259,"type":"single","stem":"井下低压馈电开关的漏电闭锁功能应在馈电开关处于什么状态时进行试验","options":["开关合闸送电后带负荷试验","开关分闸后未送电时试验","开关合闸后空载试验","开关运行中按下试验按钮"],"answer":[1],"explanation":"知识点：漏电闭锁是在开关分闸状态下检测负载侧绝缘，绝缘不合格则闭锁不能合闸。正确项对：分闸未送电时试验才能真实反映闭锁功能。错误项错在：合闸送电后负载带电，试验的是漏电保护而非闭锁；合闸空载仍属送电状态，闭锁已解除；运行中按试验按钮检验的是漏电跳闸动作，不是闭锁。"},{"id":260,"type":"single","stem":"井下电气设备隔爆外壳的隔爆结合面涂油时，应选用下列哪种处理方式","options":["涂少量凡士林或防锈油脂","涂满润滑脂填平间隙","涂油漆防止锈蚀","涂机油增加导电性"],"answer":[0],"explanation":"知识点：隔爆结合面需保持规定的间隙和粗糙度，可涂薄层防锈油脂防锈。正确项对：凡士林或专用防锈油脂薄涂不影响隔爆性能。错误项错在：涂满润滑脂会改变结合面间隙、影响隔爆；涂油漆会形成绝缘层且改变间隙，属违规；涂机油会流失且不防锈，还可能吸附煤尘。"},{"id":261,"type":"single","stem":"井下检漏继电器动作后，恢复送电前必须先做的工作是","options":["直接按复位按钮试送电","查明并排除漏电故障点","将检漏继电器退出运行","把漏电闭锁值调大后送电"],"answer":[1],"explanation":"知识点：漏电动作说明电网绝缘已低于允许值，必须查明原因。正确项对：排除故障点后才能恢复送电，否则可能引发触电或瓦斯爆炸。错误项错在：直接复位送电会再次跳闸或扩大事故；退出运行等于失去漏电保护；调大闭锁值属于破坏保护定值。"},{"id":262,"type":"single","stem":"井下使用普通万用表测量电气设备绝缘电阻时，下列做法正确的是","options":["在设备带电情况下直接测量","停电并验电放电后测量","在设备运行中测量接线端子","仅断开负荷开关后测量"],"answer":[1],"explanation":"知识点：测绝缘必须停电、验电、放电，防止残余电荷和感应电伤人。正确项对：停电验电放电后测量安全且数据准确。错误项错在：带电测量会损坏仪表并触电；运行中测量无法反映真实绝缘；仅断负荷开关电源侧仍可能带电。"},{"id":263,"type":"single","stem":"井下电气设备进行耐压试验时，试验电压应加在","options":["主回路带电部分与外壳之间","主回路相间并同时接地","控制回路与主回路之间","所有接线端子与电缆之间"],"answer":[0],"explanation":"知识点：耐压试验检验主回路对地绝缘强度，电压加在带电部分与外壳之间。正确项对：该方式能考核主绝缘对地的耐压水平。错误项错在：相间加压考核的是相间绝缘而非对地；控制回路与主回路之间不是主绝缘考核部位；端子与电缆之间不构成规定试验回路。"},{"id":264,"type":"single","stem":"井下电气作业中，发现隔爆外壳失爆但设备暂时不能停运，正确的处置是","options":["加强巡检继续运行到检修班","立即停止该设备供电并处理","用棉纱临时堵塞失爆部位","降低负荷维持到交接班"],"answer":[1],"explanation":"知识点：失爆设备在井下属于重大隐患，必须立即停电处理。正确项对：立即停电消除引爆源，是唯一安全处置。错误项错在：加强巡检不能消除失爆；棉纱堵塞不隔爆且可燃；降负荷运行仍存在电火花引爆风险。"},{"id":265,"type":"single","stem":"井下照明信号综合保护装置中，短路保护整定值应","options":["按被保护线路末端两相短路电流校验","按被保护线路首端三相短路电流校验","按变压器额定电流直接选取","按最大负荷电流的1.5倍选取"],"answer":[0],"explanation":"知识点：短路保护整定需保证线路末端最小短路电流时可靠动作。正确项对：按末端两相短路电流校验灵敏度，才能切除最远端故障。错误项错在：首端短路电流最大，不能考核灵敏度；按额定电流选取不考虑短路电流水平；按负荷电流倍数选取是过载整定思路。"},{"id":266,"type":"single","stem":"井下移动变电站高压侧停送电操作时，正确的顺序是","options":["先合高压隔离开关再合负荷开关","先合负荷开关再合隔离开关","高压隔离开关与负荷开关同时合","先合低压侧开关再合高压开关"],"answer":[0],"explanation":"知识点：隔离开关不能带负荷操作，必须先合隔离开关再合负荷开关送电。正确项对：先隔离后负荷符合操作顺序，防止带负荷拉合隔离开关。错误项错在：先合负荷开关再合隔离开关会带负荷合隔离开关；同时合无法保证顺序；先合低压再合高压易造成冲击。"},{"id":267,"type":"single","stem":"井下电气设备接地网上任一保护接地点的接地电阻值不得超过","options":["1欧","2欧","4欧","5欧"],"answer":[1],"explanation":"知识点：煤矿井下保护接地网任一点接地电阻不得超过2欧。正确项对：2欧是规程规定的限值。错误项错在：1欧要求过严不符合井下规定；4欧是地面一般电气设备接地要求；5欧更宽松，不能保证漏电保护配合。"},{"id":268,"type":"single","stem":"井下电缆在水平巷道或倾角小于45度的巷道内悬挂时，电缆与水管平行敷设的最小间距应为","options":["0.1米","0.3米","0.5米","1.0米"],"answer":[1],"explanation":"知识点：井下电缆与水管平行敷设应保持0.3米以上间距，防止水管检修时损伤电缆。正确项对：0.3米是规定的最小安全间距。错误项错在：0.1米太近易受水管作业影响；0.5米和1.0米虽更安全但不符合本题规定最小值。"},{"id":269,"type":"multi","stem":"井下进行电气设备检修时，下列哪些措施属于保证检修安全的必要环节","options":["停电后验电并放电","在开关操作把手挂停电牌","检修前检测作业地点瓦斯浓度","用普通验电笔验高压回路","检修完成后直接合闸送电"],"answer":[0,1,2],"explanation":"知识点：井下电气检修必须执行停电、验电、放电、挂牌、测瓦斯等程序。正确项对：验电放电消除残余电荷；挂牌防止误送电；测瓦斯防止电火花引爆。错误项错在：普通验电笔不能验高压回路，需用高压验电器；检修后直接送电未检查确认，属违规。"},{"id":270,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并处理完毕前，对该供电回路应采取的处置是","options":["试送一次观察是否再跳","将检漏保护退出后送电","保持闭锁状态不得送电","改用手动复位后送电"],"answer":[2],"explanation":"知识点：漏电闭锁与检漏保护动作后必须查明原因。试送、退出保护送电、手动复位送电都会掩盖故障，可能造成人身触电或引爆。"},{"id":271,"type":"single","stem":"井下电缆与压风管、供水管在巷道同一侧敷设时，电缆应位于管子上方并保持的距离是","options":["0.1m以上","0.3m以上","0.5m以上","1.0m以上"],"answer":[1],"explanation":"知识点：电缆与管路同侧敷设应在上方且间距不小于0.3m。0.1m过小易受管路检修损伤，0.5m和1.0m虽更安全但不符合规程规定值。"},{"id":272,"type":"single","stem":"井下巷道内敷设的电缆受到挤压可能损伤绝缘，最应重点检查的部位是","options":["电缆吊挂点","电缆与轨道交叉处","电缆接线盒两端","电缆与风筒接触处"],"answer":[1],"explanation":"知识点：电缆与轨道交叉处受矿车挤压、碰撞最严重。吊挂点、接线盒两端、风筒接触处虽需检查但受机械挤压风险相对较小。"},{"id":273,"type":"single","stem":"井下电气设备运行中，隔爆外壳内外表面出现锈蚀但未穿透，正确的处理方式是","options":["除锈后涂防锈油继续使用","立即升井更换外壳","用砂纸打磨后直接使用","用油漆覆盖锈蚀部位"],"answer":[0],"explanation":"知识点：隔爆面未损伤时除锈涂油可继续使用。直接升井更换过度处置，打磨会损伤隔爆面，油漆覆盖会掩盖缺陷并影响隔爆性能。"},{"id":274,"type":"single","stem":"井下供电系统采用检漏保护时，若在馈电开关负荷侧加装漏电闭锁，其动作后恢复送电的条件是","options":["漏电故障被排除且绝缘电阻合格","按下复位按钮即可送电","将开关打到试验位置后送电","等待值班电工到场后送电"],"answer":[0],"explanation":"知识点：漏电闭锁必须待故障排除、绝缘合格后方可解锁送电。按复位按钮、试验位置送电、仅等人员到场都不能确认绝缘已恢复。"},{"id":275,"type":"single","stem":"井下移动变电站低压侧漏电保护装置进行定期试验时，正确的做法是","options":["每天试验一次并记录","每周试验一次并记录","每月试验一次并记录","每季度试验一次并记录"],"answer":[0],"explanation":"知识点：井下低压漏电保护应每天进行一次跳闸试验。每周、每月、每季度均超过规定周期，不能及时发现保护失效。"},{"id":276,"type":"single","stem":"井下电气设备发生接地故障后，在故障未消除前对该设备应","options":["悬挂警示牌并禁止送电","断开接地线后送电","降低电压等级试送电","由监护人监护下送电"],"answer":[0],"explanation":"知识点：接地故障未消除前必须挂牌禁止送电。断接地线、降压试送、监护送电都可能使外壳带电或引发瓦斯爆炸。"},{"id":277,"type":"single","stem":"井下电缆连接若采用冷补胶修补，其修补后的绝缘电阻应不低于","options":["1MΩ","2MΩ","5MΩ","10MΩ"],"answer":[3],"explanation":"知识点：井下电缆冷补修补后绝缘电阻应不低于10MΩ。1MΩ、2MΩ、5MΩ均低于合格标准，运行中易发生漏电。"},{"id":278,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并处理前，对该馈电开关的正确操作是","options":["可试送电一次观察是否再跳","可退出检漏保护后送电","查明原因处理后方可送电","可增大整定值后送电"],"answer":[2],"explanation":"知识点：检漏保护动作说明存在漏电故障，必须查明原因处理后方可送电。试送电、退出保护、增大整定值都是带病运行的做法，可能引发触电或瓦斯爆炸。"},{"id":279,"type":"single","stem":"井下电气设备搬迁后重新安装，接地连接的正确做法是","options":["利用原有接地极重新连接","接地极和接地线全部重新敷设","接地线重新敷设接地极可沿用","接地极重新打设接地线可沿用"],"answer":[1],"explanation":"知识点：设备搬迁后接地极和接地线均应重新敷设并测试接地电阻。沿用原有接地极或接地线可能因锈蚀、松动、埋深不足导致接地电阻超标，不符合规程要求。"},{"id":280,"type":"single","stem":"井下使用中的电气设备绝缘电阻测定，对660V低压电缆用500V兆欧表测量，其绝缘电阻最低允许值为","options":["0.5兆欧","1兆欧","2兆欧","5兆欧"],"answer":[1],"explanation":"知识点：660V低压电缆用500V兆欧表测量，绝缘电阻不低于1兆欧。0.5兆欧偏低，2兆欧和5兆欧虽高于标准但不是最低允许值，属干扰项。"},{"id":281,"type":"single","stem":"井下防爆电气设备在运行中出现外壳温度超过规定值，正确的处置是","options":["加强通风降温后继续运行","停电检查并处理超温原因","降低负荷继续观察运行","记录温度变化暂不处理"],"answer":[1],"explanation":"知识点：防爆设备外壳超温说明内部可能过载、接触不良或散热不良，必须停电检查处理。加强通风、降负荷、只记录都不能消除内部故障根源，属于带病运行。"},{"id":282,"type":"single","stem":"井下电缆连接时，对铠装电缆钢带与接地线的连接要求是","options":["钢带与接地线焊接并可靠连接","钢带可悬空不接地","钢带通过卡子压接即可不焊接","钢带与相线一并接入接线柱"],"answer":[0],"explanation":"知识点：铠装电缆钢带必须与接地线焊接并可靠连接，保证金属护套接地。悬空、仅卡压不焊接、接入相线柱都会导致接地不可靠或短路。"},{"id":283,"type":"single","stem":"井下变电所值班人员发现高压开关柜有放电声且伴有异味，正确的第一步处置是","options":["立即断开该柜电源并报告","先记录放电频率再处理","通知检修人员到场后观察","拉开隔离开关后继续监视"],"answer":[0],"explanation":"知识点：放电声和异味说明绝缘可能击穿，必须立即断电并报告。记录、等待、仅拉隔离开关都可能延误导致短路或火灾，属于错误处置。"},{"id":284,"type":"single","stem":"井下掘进工作面电缆被矿车压伤，外护套破损露出芯线绝缘，现场电工的正确处置是","options":["用绝缘胶带缠绕破损处后送电","停电后切除损伤段重新连接","停电后仅更换外护套送电","降低负荷运行至检修班处理"],"answer":[1],"explanation":"知识点：电缆芯线绝缘受损必须停电切除损伤段重新连接并做绝缘测试。缠绕胶带、只换护套、降负荷运行都不能恢复绝缘强度，属带病运行。"},{"id":285,"type":"single","stem":"井下电气设备检修时，停电后挂牌上锁的正确做法是","options":["由检修负责人挂牌并保管钥匙","由值班员挂牌钥匙交检修人","由检修人挂牌钥匙交值班员","由检修人和值班员共同挂牌"],"answer":[0],"explanation":"知识点：停电挂牌上锁应由检修负责人执行并保管钥匙，防止他人误送电。钥匙交值班员或他人保管可能被误送电，共同挂牌责任不清。"},{"id":286,"type":"multi","stem":"井下电气设备入井前必须进行的防爆检查项目包括","options":["隔爆外壳有无裂纹和变形","隔爆接合面间隙是否符合规定","电缆引入装置是否齐全紧固","设备内部是否清洁无杂物","外壳是否涂有防锈油漆"],"answer":[0,1,2],"explanation":"知识点：入井前防爆检查包括外壳完整性、接合面间隙、引入装置紧固等。外壳裂纹变形、间隙超标、引入装置缺失都会破坏隔爆性能；内部清洁和外壳油漆不属于防爆检查必查项，油漆反而可能影响接合面。"},{"id":287,"type":"single","stem":"井下检漏保护装置动作后，在未查明原因并排除故障前，对该供电回路应采取的处置是","options":["试送电一次观察是否再跳","将该回路退出运行并挂牌","把检漏保护短接后继续供电","调大检漏动作电阻值再送电"],"answer":[1],"explanation":"知识点：漏电闭锁与故障处置。检漏动作说明回路绝缘可能已损坏，必须退出运行、挂牌并查明原因；试送电可能造成人身触电或瓦斯爆炸；短接检漏属严重违章；调大动作值会失去保护作用。"},{"id":288,"type":"single","stem":"井下电气设备进行停电检修时，验电、放电之后还必须完成的关键一步是","options":["挂接地线并三相短接","测量绝缘电阻","清理设备表面煤尘","通知调度送电时间"],"answer":[0],"explanation":"知识点：停电检修安全程序。验电、放电后必须挂接地线并三相短接，防止误送电和感应电荷伤人；测绝缘电阻是检修后项目；清理煤尘是辅助工作；通知送电时间是送电前程序。"},{"id":289,"type":"single","stem":"井下低压橡套电缆连接电气设备时，电缆护套伸入设备接线腔的长度应满足的要求是","options":["护套剥除后芯线全部裸露","护套伸入腔内5至15毫米","护套与接线端子齐平","护套剥除长度等于接线腔深度"],"answer":[1],"explanation":"知识点：电缆引入装置密封要求。护套应伸入接线腔5至15毫米，使密封圈能有效抱紧护套；芯线全裸露会失去密封；护套与端子齐平无法密封；剥除长度等于腔深会使护套无法进入密封圈。"},{"id":290,"type":"single","stem":"隔爆型电气设备的隔爆外壳上，用于保证外壳强度且不允许随意更换的部件是","options":["观察窗玻璃","紧固螺栓","接线端子","内部绝缘座"],"answer":[1],"explanation":"知识点：隔爆外壳紧固件要求。紧固螺栓的规格、强度等级和数量是隔爆性能的保证，缺失或代用会降低耐爆强度；观察窗玻璃属于透明件有专门要求；接线端子和绝缘座不承受爆炸压力。"},{"id":291,"type":"single","stem":"井下使用摇表测量电气设备绝缘电阻时，正确的操作顺序是","options":["先摇动手柄再接入被试设备","先接好线再快速摇动手柄","先接好线再均匀摇动手柄","先短接两表笔再摇动手柄"],"answer":[2],"explanation":"知识点：绝缘电阻表使用。应先接好线再均匀摇动手柄，转速稳定后读数；先摇后接会在接入瞬间产生高压冲击；快速摇动转速不稳读数不准；短接表笔摇动会损坏仪表。"},{"id":292,"type":"single","stem":"井下局部通风机实行“三专”供电，其中“三专”指的是","options":["专用变压器、专用开关、专用电缆","专用线路、专用开关、专用电动机","专用变压器、专用线路、专用保护","专用开关、专用电缆、专用接地"],"answer":[0],"explanation":"知识点：局部通风机三专供电。三专指专用变压器、专用开关、专用电缆，保证局部通风机可靠供电；专用线路、专用电动机、专用保护、专用接地均不属于三专内容。"},{"id":293,"type":"single","stem":"井下电气设备接地网上，任一点接地电阻值应满足的要求是","options":["不超过1欧姆","不超过2欧姆","不超过4欧姆","不超过10欧姆"],"answer":[1],"explanation":"知识点：井下接地网接地电阻要求。任一点接地电阻不得超过2欧姆，以保证漏电时保护可靠动作；1欧姆要求过严；4欧姆和10欧姆是地面或其他场合的常见值，不适用于井下接地网。"},{"id":294,"type":"single","stem":"隔爆型电气设备接线腔内电缆芯线与端子连接时，下列做法正确的是","options":["芯线压接后露出端子过长","每个端子只接一根芯线","多根芯线拧在一起接入同一端子","芯线绝缘层伸入端子压接"],"answer":[1],"explanation":"知识点：接线腔接线工艺。每个端子只接一根芯线，保证接触可靠；芯线露出过长易造成短路；多根拧接接触不良且易发热；绝缘层伸入端子会形成虚接发热。"},{"id":295,"type":"single","stem":"井下掘进工作面因检修需要临时停止局部通风机运转，恢复通风前必须先做的工作是","options":["直接启动通风机恢复通风","检查瓦斯浓度符合规定后启动","先启动电气设备再启动通风机","先撤人再启动通风机"],"answer":[1],"explanation":"知识点：停风后恢复通风程序。停风后可能积聚瓦斯，必须先检查瓦斯浓度符合规定再启动通风机；直接启动可能引起瓦斯爆炸；先启动电气设备违反送电程序；撤人不是恢复通风前的首要检查步骤。"},{"id":296,"type":"single","stem":"井下检修电气设备时，验电后确认无电，接下来按规定应首先做的是哪一步","options":["对可能送电到检修设备的开关把手加锁并悬挂警示牌","用接地线对检修设备各相导体放电并三相短接接地","直接开始拆卸设备接线腔内的导电螺栓","用万用表再次测量设备进出线端子确认无电压"],"answer":[1],"explanation":"知识点为停电检修安全程序：验电确认无电后必须先放电并装设接地线，防止反送电和残余电荷伤人。加锁挂牌应在停电后验电前环节完成，且不能替代放电接地；直接拆线未做放电接地有触电风险；万用表复测不能代替放电接地保护。"},{"id":297,"type":"single","stem":"矿用隔爆型电气设备隔爆接合面出现轻度锈蚀但未超过规定间隙时，正确的处理方法是","options":["用砂纸打磨除锈后涂适量防锈油并测量间隙","用棉纱蘸汽油擦拭锈迹晾干后直接复装","用扁铲把锈层铲掉再抹一层润滑脂防锈","把接合面刷一层油漆覆盖锈斑防止继续腐蚀"],"answer":[0],"explanation":"知识点为隔爆接合面维护：锈蚀未超限时可用砂纸打磨除锈、涂防锈油并复测间隙，保证隔爆性能。汽油擦拭不能除净锈层且挥发后无防护；扁铲铲削会破坏接合面平面度和间隙；刷油漆会增大间隙并影响隔爆，属错误做法。"},{"id":298,"type":"single","stem":"井下低压馈电开关检漏保护装置动作后，在未查明原因前正确的处置是","options":["断开检漏保护退出运行后逐台试送各分路","按下复位按钮试送一次观察能否维持供电","先合上总开关再逐一合分路找出故障支路","查明并排除漏电故障点后方可恢复送电"],"answer":[3],"explanation":"知识点为漏电闭锁与检漏保护：检漏动作说明存在漏电或绝缘降低，必须查明排除故障后才能送电。退出检漏运行属于甩保护；复位试送和先合总开关再试分路都属于带故障强行送电，可能引发触电或瓦斯爆炸。"},{"id":299,"type":"single","stem":"某掘进工作面局部通风机专供线路停电检修，检修完成后准备恢复送电，正确的做法是","options":["检修负责人确认人员撤出、拆除接地线后通知送电","由瓦斯检查员确认瓦斯不超限后直接合闸送电","由跟班队长电话通知变电所可以试送电","检修电工自己确认接线无误后合闸试送风机"],"answer":[0],"explanation":"知识点为停送电制度：恢复送电必须由检修负责人确认人员撤离、接地线拆除、具备送电条件后通知送电。瓦斯检查员只负责瓦斯检测不能决定送电；跟班队长电话通知缺少检修负责人确认；电工自行合闸违反谁检修谁负责确认、专人联系送电的程序。"},{"id":300,"type":"multi","stem":"井下变电所一台BKD9型低压馈电开关在合闸瞬间频繁跳闸，显示屏无故障代码，现场电钳工排查时下列哪些处置环节存在错误","options":["先断开上一级隔离开关并验电放电，再打开开关本体检查内部接线","用同型号备用插件替换保护插件后直接合闸试送电观察是否动作","断开负荷侧电缆后用摇表测量电缆相间绝缘电阻并记录数值","将漏电闭锁试验旋钮转至退出位置后合闸判断是否漏电引起跳闸"],"answer":[1,3],"explanation":"知识点：矿用隔爆馈电开关跳闸排查的安全程序与漏电闭锁功能。A正确，检修前必须断电、验电、放电，是隔爆设备检修的基本安全步骤。B错误，更换保护插件后应先检查整定值与漏电闭锁功能，不能直接合闸试送电，否则可能扩大故障范围。C正确，断开负荷侧测电缆绝缘是区分开关本体故障与线路故障的常规手段。D错误，漏电闭锁是保护功能，人为退出再合闸等于甩掉漏电保护，属于严重违章操作，应通过正常试验按钮检查闭锁功能。"}]}